Navien Air Conditioner: Evacuation target after component replacement
Evacuation target after component replacement on a Navien air conditioner: Pull the system down to this vacuum before opening the service valves and charging.
Applies to: NAA17V36 and NAA17V60
How to fix evacuation target after component replacement: step by step
- Pull the vacuum to 350 microns with a vacuum pump.
- Open the service valves after the vacuum is complete.
- Charge refrigerant if a recovery unit is used.
If the unit shows an error code, look it up: Navien Air Conditioner codes
More commissioning tips for air conditioner
Source: Navien NAA air conditioner service manual, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.