Refrigerant charging mode on Infinity control (25VNA8/24VNA9)

Carrier · Carrier Infinity 25VNA8/24VNA9 communicating systems

Opened from the Installation and Service screen to check or set charge. Offers weigh-in or heating check methods; the heating check runs at stage 5 with matched fans and counts down while stabilizing. Service-valve subcooling shows only when temperatures are in range.

  1. On the Infinity control open Installation and Service, then Refrigerant Charging
  2. Pick the charge method on the Charging Mode Selection screen
  3. Wait for the stabilization countdown before reading pressures

Charging the outdoor unit

Goodman · Communicating two stage or inverter outdoor units

A cooling call right after power-up runs the outdoor unit at full capacity, which is useful for charging.

  1. Turn on power to the indoor and outdoor units.
  2. Give a cooling call (Y or Y+G).
  3. The outdoor unit runs at full capacity until the call is removed.
  4. If the system runs in low stage, cycle power and give the cool call again to get full capacity.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.