Viessmann Boiler: Viewing ionization current
Viewing ionization current on a Viessmann boiler: Shows the flame ionization current during operation. The reading is shown in 1/10 μA.
Applies to: Vitocrossal 200 CM2 burner control unit
How to fix viewing ionization current: step by step
- Press S for longer than 2 seconds until the menu item flashes.
- Scroll with Y until 5 shows under Service, then press S.
- Scroll with Y until 3 shows under Service, then press S. The ionization current shows under Service during operation (e.g. 30 = 3.0 μA).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
More service & test modes tips for boiler
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 45. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.