Service & test modes: Boiler tips (part 9 of 10)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on service & test modes for boiler. Check each one against the manual for your exact model before acting.

View sensor and relay information in Service mode

Viessmann · Versatronik 200 service mode

Service mode gives access to test and information screens for the circuits. The manual prints the word User on the selection key, which is likely meant to be Service; confirm on site.

  1. Press the Home button to show the Main Menu.
  2. Turn the rotary dial until Service is shown on the screen.
  3. Press the key beside the word shown to select the menu option.
  4. Select the circuit you want to view tests or information for.
  5. Press Cancel to leave the current screen.

View solar energy yield graph

Viessmann · Vitotronic 300-K MW1B with solar thermal system

Shows solar energy yield for the past 7 days as a graph. The flashing line marks the current day, which is not finished yet.

  1. Open the extended menu.
  2. Select Solar energy.

View the burner fault memory

Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The last 10 faults are stored and can be scrolled. The display closes on its own if no key is pressed for 20 seconds.

  1. Hold S for more than 2 seconds until the indicator flashes.
  2. Press Y until '4' shows under Service.
  3. Press S. '4' shows under Status.
  4. Press Y or B to choose '1' (display fault codes) or '2' (detail fault codes).
  5. Press S to open the selected view.
  6. Press Y or B to scroll through the fault codes, from most recent to oldest.

View the fault history

Viessmann · Vitotronic 300 GW6B boiler control unit

The 10 most recent faults are stored, including those already fixed, sorted by date. Fault history can be cleared.

  1. From the home screen, tap Menu, then Service.
  2. Enter the viservice password.
  3. Tap History of faults.
  4. Tap ? in a fault to see more information.
  5. Tap Reset to delete the list.

View the fault history (last 10 faults)

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The control keeps the 10 most recent faults, including resolved ones, sorted by date. Use this to see what happened before a call.

  1. Press OK and the second service button together for about 4 seconds.
  2. Select "Fault history".
  3. Select "Display?" and press OK to read each fault code.

View the fault memory (error history)

Viessmann · Vitocontrol-S VD2/CT3/CM2 with Vitotronic 100 GC1

The control unit stores the last 10 fault codes. Each entry shows its order, with 1 being the last fault. Saved codes can be deleted all at once. Button symbols on the printed page are not readable, so the key names are not given.

  1. Press the two keys together for about 2 seconds to open the error history.
  2. Scroll through the entries with the arrow keys to view the individual fault codes.
  3. Press the marked key to delete all saved fault codes.
  4. Press the marked key again to exit.

Viewing all time phases at a glance

Viessmann · HK1S and HK3S

Shows the preset time phases on a time-slot graphic without changing them.

  1. Open the hinged cover on the programming unit.
  2. Press the heating time program button and the scan button together.
  3. The preset phases appear on the time-slot graphic.
  4. Close the hinged cover.

Viewing and clearing the fault memory (error history)

Viessmann · Vitotronic 300-K MW1S

The control keeps the last 10 fault codes. Each one is shown with its order of occurrence.

  1. Press the two buttons shown on page 105 together for about 2 seconds.
  2. Scroll through the codes with the up or down button. Code 1 is the last fault.
  3. To delete all saved codes, use the delete button shown on page 105.
  4. Press the button shown on page 105 to exit.

Viewing ionization current

Viessmann · Vitocrossal 200 CM2 burner control unit

Shows the flame ionization current during operation. The reading is shown in 1/10 μA.

  1. Press S for longer than 2 seconds until the menu item flashes.
  2. Scroll with Y until 5 shows under Service, then press S.
  3. Scroll with Y until 3 shows under Service, then press S. The ionization current shows under Service during operation (e.g. 30 = 3.0 μA).

3-way valve test (combi models only)

Weil-McLain · Combi models 110, 150, 199

Tests whether the DHW/heating 3-way valve actuator moves and the valve shaft works.

  1. Go to DIAGNOSTICS, Manual Test Mode.
  2. Make sure the boiler is in Standby with no heat calls active.
  3. Press edit and select the desired 3-way valve position.
  4. Remove the actuator (procedure in Figure 138, p. 158) and watch the motor shaft as you change position.
  5. The shaft should slide in and out with no play in the extended position.
  6. Push the shaft in the sanitary shutter with a blunt object; it should compress against the valve spring.
  7. If the shaft will not move or sticks compressed, follow the flow manifold cleaning procedure on p. 158.

Combustion adjustment screw directions

Weil-McLain · ECO Tec 80/110/150/199 gas valve

Use the throttle screw for high fire and the offset screw for low fire. Adjust in the direction that changes CO2 as needed.

  1. Throttle screw: turn counterclockwise to increase CO2, clockwise to decrease CO2.
  2. Offset screw (80 and 110 only, under sealed cap): turn clockwise to increase CO2, counterclockwise to decrease CO2.
  3. Adjust high fire first with the throttle screw, then force low fire and adjust the offset screw.
  4. Reinstall the cap over the offset screw after adjusting.

Connect to the boiler over Bluetooth

Weil-McLain · ECO Tec Series 3 boilers with WM ProTools app

Bluetooth is needed to access configuration settings. Bluetooth stays on for 30 minutes of inactivity.

  1. Swipe right on the display to reach the Menu screen.
  2. Press the BLUETOOTH button.
  3. Toggle Bluetooth on with the blue toggle.
  4. Turn on Bluetooth on the smartphone.
  5. Open the WM ProTools app, press Connect, then Connect to Boiler, and select the WM boiler.
  6. If no boiler appears, toggle the boiler Bluetooth off and on again. Wait for the display to connect before leaving that screen.

DIAGNOSTICS menu overview

Weil-McLain · Ultra U-Control diagnostics

The DIAGNOSTICS menu gives temperatures, inputs, outputs, error counts, lockout history, software versions and a manual test mode.

  1. Open DIAGNOSTICS in the contractor menus.
  2. Review TEMPERATURES for system supply, return, boiler out and in, flue, and outdoor readings.
  3. Review INPUTS for priority demands, analog input, manual and auto limits, low water cutoff, blower tachometer and flame signal.
  4. Review OUTPUTS for gas valve, circulators, blower signal, additional heat demand and alarm.
  5. Review ERRORS for control fault, ignition retries, and manual and auto reset counts.
  6. Review LOCKOUT HISTORY for the last three lockouts.
  7. Use MANUAL TEST MODE with FORCE RATE AUTO to test firing rate when required.

Diagnostics readouts for troubleshooting

Weil-McLain · Ultra Series 4 boilers, U-Control

Live readings found under Diagnostics. Use them to see what the boiler sees.

  1. Temperatures: System Supply, System Return, Boiler Out1 and Out2, Boiler In1, Flue1 and Flue2, Outdoor.
  2. Inputs: Priority 1, 2 and 3 calls, Analog Input (0-10 VDC on P15 #5 and #6), Manual Limit (P13-1 and P13-2), Auto Limit (P13-3 and P13-4), Low Water Cutoff (P12-3 and P12-4), Blower Tach rpm, Flame Signal.
  3. Outputs: Gas Valve, Circulators 1-3, Blower Signal (% of rate), Additional Heat Demand, Alarm contact, Analog Output (P16 #1 and #2).
  4. Errors: Control Fault count, Ignition Retries, Manual Reset count, Auto Reset count.
  5. Software Versions: Display, Main Micro and Second Micro.

Do not measure gas valve outlet pressure

Weil-McLain · All Ultra boilers during propane conversion

Manometer fluid can contaminate and damage the gas valve. Outlet pressure must not be checked during conversion.

  1. Do not connect a manometer to the gas valve outlet.

Force a firing rate for testing

Weil-McLain · Evergreen Pro Series 2 boilers

Manual Test Mode lets you force a modulation rate during a call for heat. Return it to auto afterward.

  1. Open DIAGNOSTICS and go to Manual Test Mode.
  2. Set Force Rate to the rate needed for the test.
  3. When testing is finished, set Force Rate back to auto.

Force a firing rate in Manual Test Mode

Weil-McLain · Ultra Series 4 boilers, U-Control

Forces a fixed firing rate during a call for heat. Leave it on Auto for normal operation.

  1. Open Manual Test Mode in the U-Control menu.
  2. Select Force Rate and choose Low, Med, High or Auto (default Auto).
  3. Watch Status, Target, Flame Signal, Blower Signal and Blower Tach while forced.
  4. Return Force Rate to Auto when testing is done.

Force firing rate in manual test mode

Weil-McLain · U-Control on Ultra Series 4

Manual test mode lets the technician hold the burner at high fire, low fire or normal auto control for combustion checks.

  1. Enter the installer menus and go to Manual test mode (menu location shown in Figure 115, page 102).
  2. Force firing rate to MAX (high fire) and check the flame and combustion.
  3. Force firing rate to MIN (low fire) and check again.
  4. Set firing rate back to AUTO (normal operation) when finished.

Ignition difficulty after coarse adjustment

Weil-McLain · ECO Tec gas valve

If the boiler will not light after coarse gas valve settings, add throttle opening in small steps. Do not exceed one full turn in total.

  1. Turn the throttle screw counterclockwise an additional 1/4 turn and try to light again.
  2. Repeat up to a total of one full turn.
  3. If the boiler still will not ignite, or the analyzer reads below 10% O2 during combustion analysis, contact WM Technologies Technical Services.

Integrated low water cutoff test button

Weil-McLain · Integrated type low water cutoff

Test the integrated low water cutoff using the control's LWCO TEST button while the burner is firing.

  1. With the burner firing, press the LWCO TEST button on the control.
  2. Confirm the burner shuts off.

LWCO TEST button check

Weil-McLain · EG and PEG Series 7 boilers with Unity-CI control

Use the LWCO TEST button on the control to confirm the low water cutoff shuts the burners down and restarts them.

  1. With the burners operating, press and hold the LWCO TEST button on the control.
  2. Confirm the burners go off, the circulator keeps running and LWCO is displayed.
  3. Release the LWCO TEST button and confirm the ignition sequence resumes.

Manual test mode (force firing rate)

Weil-McLain · ECO Tec Series 3 gas boilers

Forces the boiler to a set firing rate for testing.

  1. Go to DIAGNOSTICS and open Manual Test Mode.
  2. Call for heat and wait until the burner is lit.
  3. Press EDIT and select the FORCE RATE.
  4. The rate is held for 30 minutes.
  5. Test mode resets at the end of the heat demand.
  6. If the timer runs out, the boiler returns to AUTO and keeps running if demand still exists.

Manual test mode for firing rate

Weil-McLain · Ultra 80, 105, 155, 230, 299, 399

Forces the boiler to low, medium (ignition) or high fire for checks. Low fire is adjusted in the boiler setup menu.

  1. Navigate to Manual test mode on the U-Control (see Figure 115, page 102).
  2. Set the firing rate to MINIMUM, MEDIUM or MAXIMUM as needed for the check.
  3. Return to normal operation after testing.

Manual Test Mode for forcing firing rates

Weil-McLain · SVF 1500-3000

Manual Test Mode locks the boiler at low or high fire so combustion and rpm can be checked. Use it for combustion checks and gas valve adjustment.

  1. Navigate to DIAGNOSTICS and select Manual Test Mode.
  2. Lock the boiler at low or high fire.
  3. Check the rpm shown against the blower speed table.
  4. Return the firing rate to Auto when finished.

Manual Test Mode for pump voltage and firing rate

Weil-McLain · Evergreen Series 2 with variable speed pump output

Manual Test Mode shows live readings and lets you force the firing rate. It is also used to save the variable pump max and min voltages.

  1. Open PUMP SETTINGS from the contractor menus and select Manual Test.
  2. Read status, inputs, modulation source, temperatures, blower signal and speed, flame signal, and pump volts on the screen.
  3. To set the max pump voltage, force rate to HIGH and save as MAX VOLTS.
  4. To set the min pump voltage, force rate to LOW and save as the min voltage.

Manual test of the relief valve

Weil-McLain · Ultra Series 4 gas-fired water boiler relief valve

Checks that the relief valve opens and reseats properly. The discharge line must be piped to a safe place before testing.

  1. Confirm the relief valve outlet is piped to a safe discharge location where scalding is not possible.
  2. Read the pressure/temperature gauge and confirm the system is pressurized.
  3. Lift the relief valve top lever slightly so water flows through the valve and discharge piping.
  4. If water flows freely, release the lever and let the valve seat.
  5. Watch the discharge pipe after it has drained. If the valve weeps, lift the lever again to try to clean the seat.
  6. If the valve still weeps, have a qualified service technician inspect the valve and system.
  7. If no water flows when the lever is fully lifted, the valve or discharge line may be blocked. Shut the boiler down per page 9 and call a qualified service technician.

Read live operating data on the boiler information screen

Weil-McLain · ECO Tec control

The homeowner boiler information screen shows the current sequence status and sensor values useful for field checks.

  1. From the home screen, open the menu and select the boiler information screen.
  2. Check STATUS for the current sequence and active priority.
  3. Check INPUT STATUS for each call for heat and the 0-10V value if used.
  4. Check PUMPS/AUX for active outputs and BOILER OUT/IN for water temperatures.
  5. Check TARGET TEMP and MODULATION RATE (blower speed).
  6. Check DHW FLOW and DHW TEMP on combi models only.

Read pilot flame sense value

Weil-McLain · EG water boilers, pilot ignition

The Advanced Menu shows the pilot flame signal the control measures. A value of 60 or higher means no flame. A good flame reads below 60, and a stronger flame gives a lower number.

  1. Open the Advanced Menu.
  2. Go to Diagnostics, then Inputs & Outputs.
  3. Select Flame Sense to read the pilot flame value.
  4. Compare the reading with the threshold: 60 is no flame, and lower values mean better flame quality.

Read the last six lockouts (fault history)

Weil-McLain · ECO Tec Series 3 control display

Shows counts and details of recent lockouts, useful before clearing or resetting anything.

  1. Open DIAGNOSTICS in the Contractor Menus.
  2. Select FAULT HISTORY and press the right arrow key.
  3. Record Ignition Retries, Manual Reset Count and Auto Reset Count.
  4. Select LOCKOUT HISTORY # and press the right arrow key for details, up to six.

Read the last three lockout histories

Weil-McLain · Ultra 80, 105, 155, 230, 299, 399

Lockout history is stored in the U-Control. Record the first four data records before clearing anything.

  1. Scroll to DIAGNOSTICS and press enter.
  2. Scroll to ERRORS and press enter.
  3. Scroll to LOCKOUT HISTORY # and press enter.
  4. Choose MANUAL RESET or AUTO RESET and press enter to see the fault recorded.
  5. Press the left arrow to return to the lockout history list, then select another history to see boiler conditions at that lockout.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.