Viessmann Boiler: Flue length calculation examples
Flue length calculation examples on a Viessmann boiler: Worked examples for the entered Flue System Length.
Applies to: Vitocrossal 200 CI2
How to fix flue length calculation examples: step by step
- CI2 399 with burner filter: 75 ft + 0 ft + 33 ft = 108 ft (33 m) entered.
- CI2 750 with no intake accessory: 150 ft (46 m) entered.
- CI2 1500 with direct vent inline filter: 75 ft + 60 ft + 98 ft = 233 ft (71 m) entered.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
More commissioning tips for boiler
Source: Vitocrossal 200 CI2 service instructions, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.