Factory date, time and daylight saving
Viessmann · Vitotronic 300 GW2
Date and time are preset at the factory in CET. Daylight saving changeover happens automatically.
Factory default settings and commissioning
Viessmann · Vitocrossal 300 CA3B Dual Fuel
The Vitotronic 300 GW6C ships with factory defaults. The boiler can be started with these, but commissioning should be completed with the Commissioning Assistant or System Configuration in the service menu. Defaults include standard room temperature 68°F (20°C), DHW setpoint 122°F (50°C), frost protection, automatic daylight saving time, and saved settings after power loss.
- Complete commissioning with the Commissioning Assistant or System Configuration in the service menu.
- Have the heating contractor set the date and time and match the control to local conditions.
Factory setup and parts ordering
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Units ship factory tested and calibrated for natural gas. Gas valve adjustment is normally not needed at startup. Always give the 16-digit boiler serial number (bar code label) or the 12-digit ASME/NB serial number when ordering parts, because some parts are not reverse compatible with earlier versions.
Factory-calibrated gas valve
Viessmann · Vitodens 200-W B2HA 45, 60
The B2HA boiler is factory tested and calibrated. Gas valve adjustments are typically not needed at field start-up.
Factory-preset behaviour after commissioning
Viessmann · Vitocrossal 200 CI2 after commissioning
The boiler is preset at the factory and is ready for use after commissioning. Frost protection for the boiler and DHW tank is on. Wintertime and summertime changeover is automatic. Date and time are set by the contractor and can be changed. All settings are kept during a power failure. Commissioning and local matching are done by the contractor.
- Confirm date and time after commissioning if the site requires it.
- Check that frost protection is active on the boiler and DHW tank.
- Leave settings as set by the contractor unless the user requests a change.
Fault message on first start-up of multi boiler system
Viessmann · Multi boiler systems with Vitocrossal 200 CM2 boilers
In a multi boiler application with a Vitocrossal 200 CM2 boiler, a fault message appears at first start-up. It means the boiler controller commissioning is not finished yet.
- Acknowledge the fault message.
- Complete the commissioning process.
Feedback contact D: remove jumper
Viessmann · Feedback contact D on the boiler control
The feedback contact for on-site safety equipment or indoor air damper is wired to terminal D.
- Remove the jumper between 25 L and 26 L before connecting feedback contact D (the factory setting has the jumper fitted).
Field conversion from natural gas to LP gas
Viessmann · Vitocrossal 300 CU3A natural gas and LP gas
Boiler ships set for natural gas. Field conversion to LP gas uses the conversion label kit.
- Use the NG to LPG conversion label kit, which includes instructions and labels.
- Follow the kit instructions to convert the boiler to LP gas.
- Convert back to natural gas with the same process if required.
Field pump sizing for underfloor layouts
Viessmann · Vitodens 200-W B2HA 45, 60 underfloor heating systems
Sizing of the field-supplied pump is critical in layouts with a mixing valve and system separation. An undersized pump can cause short-cycling or improper boiler operation. Viessmann strongly recommends a low-loss header and a boiler pump here.
- Check the boiler supply head pressure drop on page 28.
- Size the field-supplied pump against that drop.
- Use a low-loss header and a boiler pump in the underfloor system layout.
Field-verify piping and install a low water cut-off where required
Viessmann · Vitodens 200-W B2HB system piping
The piping examples are simplified concepts. The installer must field-verify all piping and components, and a low water cut-off (LWCO) is required where local codes call for one.
- Field-verify all piping and componentry against the drawing.
- Install a low water cut-off where local codes require it.
- Confirm proper installation and function, which is the heating contractor's responsibility.
Fill the condensate siphon before start-up
Viessmann · Initial start-up
Flue gases can come out of the condensate drain at first start-up if the siphon is dry.
- Pour at least 10 fl oz (0.3 L) of water into the boiler condensate adaptor before start-up.
Fill the condensate trap before commissioning
Viessmann · Vitodens 100-W B1HE/B1KE
The trap must hold water before start-up. Flue gas can escape from the condensate drain during commissioning.
- Pour at least 10 oz (0.3 L) of water into the flue gas connection.
- If there is a freeze risk, fill the trap only just before commissioning.
Fill the flue gas siphon before start-up
Viessmann · Start-up
An unfilled siphon can let flue gas escape into the room.
- Undo fitting A on the siphon B and remove the siphon.
- Fill the siphon with water.
- Refit the siphon.
Fill the heating system
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Fill the system through the boiler fill connection with the filling function.
- Flush the whole heating system before filling. Use potable water only.
- Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
- Open system isolation valves at C and D if installed.
- Check the expansion tank pre-charge. If it is below system static pressure, raise it to just above system pressure.
- Connect a hose to the boiler fill tap and fill at boiler fill BF while draining air from boiler drain BD.
- Activate the filling function from the service menu and end it with OK.
Fill the siphon trap before commissioning
Viessmann · Condensate siphon trap
Only commission the boiler once the siphon trap is full of water.
- Check that the siphon trap has been filled with water.
- Only then continue with commissioning.
Filling and purging programs (20 min auto-stop)
Viessmann · Vitodens 200-W B2HE 85, 120, 150, 199
Purging cycles the pump 30 s on/off and toggles the diverter valve for 20 min with the burner off. Filling parks the diverter valve in the middle and runs the pump; both stop by themselves after 20 min.
- Service menu > Service functions > Filling or Purging
- Program ends automatically after 20 min; exit Service to stop earlier
Filling the condensate siphon
Viessmann · Vitocrossal 200 CM2 186 to 311 boilers
Fill the siphon before start-up so flue gas cannot escape through the drain.
- Undo siphon cup A and fill it with water.
- Check that condensate drains freely.
- Refit siphon cup A.
Fire at the appliance
Viessmann · All models
If fire comes from the boiler, act at once.
- Call the fire department immediately.
- Shut down the boiler and close the fuel shut-off valves.
- Only fight the fire if qualified, using a tested class ABC extinguisher.
First start-up codings on the control unit
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
The control unit is preset, but several codings must be set on site. Language, date and time, temperature units, system layout and elevation can be changed at start-up.
- Switch on the main switch and all network switches on the control units.
- Switch on the control unit. Start-up begins automatically.
- Set language, date and time, temperature units, system layout and elevation as needed.
- Confirm each entry. When asked 'Do you want to make further changes', answer as required.
First start-up of the control unit
Viessmann · Vitocrossal 300 CA3B Dual Fuel boilers, control unit start-up
The control unit comes pre-set, but several codings still need to be set on site. Switch on the main switch and all network switches first, then the control unit switch. Start-up runs by itself. Language, date and time, temperature units, system layout and elevation can be changed at this point. Confirm each one, then answer the prompt asking whether further changes are needed.
- Switch on the main switch and all network switches on the control units.
- Switch on the control unit. Start-up begins automatically.
- Set language, date and time, temperature units, system layout and elevation as required.
- Confirm each entry, then answer 'Do you want to make further changes'.
First start-up settings
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
The control unit comes pre-set, but several codings must be set individually before the system runs.
- Turn on the main switch and all network switches on the control units.
- Switch on the control unit. Start-up begins automatically.
- Set language, date and time, temperature units, system layout and elevation as required.
- Confirm with OK. When asked whether you want to make further changes, answer as needed.
Flow ratio for radiator plus underfloor circuits
Viessmann · Vitodens 200-W B2HA 45, 60 layout 4
When a radiator circuit and an underfloor circuit with a 3-way mixing valve share the boiler, the radiator circuit's water flow must be at least 30% greater than the underfloor circuit's. The total of both circuits must stay below the boiler's maximum water flow.
- Confirm the radiator circuit flow is at least 30% greater than the underfloor circuit flow.
- Confirm the combined flow is below the boiler maximum on page 29.
Flue gas damper coding (0a) during commissioning
Viessmann · All applications, Vitotronic 300 GW6B
The flue gas damper coding is set to 0a:1 (with damper) in all applications by default.
- If the boiler has no flue gas damper, set coding 0a to 0a:0 during commissioning.
- If coding 0a is not set in the commissioning assistant, the burner checks for a damper and its function can only be adjusted at the burner control.
Flue gas damper coding during commissioning
Viessmann · All Vitotronic 300 GW6B applications
Flue gas damper coding address 0a defaults to 0a:1 (damper fitted) in all applications. If no flue gas damper is used, set it to 0a:0. If it is not changed at the control unit during commissioning, the burner checks for a damper itself and the damper function can then only be set at the burner control.
- Check whether a flue gas damper is fitted.
- If none is fitted, set coding address 0a to 0a:0 during commissioning or on Coding level 1.
Flue gas test point
Viessmann · Vitorond 200 VD2 flue test point
Create a flue gas test point on the vent pipe for combustion testing. The printed hole size is partly unreadable; 10 mm is the value shown.
- Drill a 10 mm hole on the side of the vent pipe.
- Place the hole about two to three times the vent pipe diameter away from the boiler flue gas collar.
- Seal and insulate the vent pipe after drilling.
Flue length calculation examples
Viessmann · Vitocrossal 200 CI2
Worked examples for the entered Flue System Length.
- CI2 399 with burner filter: 75 ft + 0 ft + 33 ft = 108 ft (33 m) entered.
- CI2 750 with no intake accessory: 150 ft (46 m) entered.
- CI2 1500 with direct vent inline filter: 75 ft + 60 ft + 98 ft = 233 ft (71 m) entered.
Flush and pressure-check the heating water side
Viessmann · Vitodens 200-W B2HA 45, 60
Flush the heating system thoroughly, especially before connecting to an existing system. Maximum operating pressure is 4 bar (60 psig) and test pressure is 6 bar (90 psig). Pressures above these values are not covered by warranty.
- Flush the heating system thoroughly before connecting the boiler.
- Connect the boiler supply and return to the heating system.
- Keep operating pressure at or below 4 bar (60 psig).
- Keep test pressure at or below 6 bar (90 psig).
Flush existing piping before connecting a retrofit boiler
Viessmann · Retrofit installations
On retrofits, a previously used heating system must be flushed to remove sludge and debris. Failure to flush can restrict flow or cause deposits and boiler failure, which is not covered by warranty.
- Flush the piping with city pressure water at 50 to 60 psi before connecting the boiler.
- Install magnetic filtration; Viessmann recommends it.
Flush existing system before connecting boiler
Viessmann · Vitocrossal 200 CI2 399 to 2000
When the boiler is piped into an existing system, flush the heating system first to remove dirt and sludge. Sludge settles in the boiler and can cause hot spots, noise and water-side corrosion. Damage from these impurities voids the warranty. Water treatment should be considered where mineral content or hardness is high.
- Flush the existing heating system completely before connecting the boiler.
- Consider water treatment in areas with high mineral content or hardness.
- Refer to the Service Instructions for water quality guidelines.
Flush piping on retrofit installs before connecting the boiler
Viessmann · Retrofit applications on CA3B Dual Fuel boilers
Existing piping must be flushed before the boiler is connected. Skipping this can cause restricted flow and deposits that lead to boiler failure, and that failure is not covered under warranty.
- Flush the existing piping with city pressure water at 50-60 psi to remove sludge and contaminants.
- Install magnetic filtration if possible (recommended).
- Flush the whole heating system piping again if it is connected to a boiler in a retrofit.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.