Viessmann Boiler: Cold fill pressure and boiler filling
Cold fill pressure and boiler filling on a Viessmann boiler: Cold water fill pressure must match the expansion tank pressure. Do not let the cold fill pressure go above 18-20 psig. Fill only with suitable water, because poor water quality can damage the boiler.
Applies to: Vitocrossal 200 CI2 399 to 2000
How to fix cold fill pressure and boiler filling: step by step
- Set cold water fill pressure equal to the expansion tank pressure.
- Keep cold fill pressure at or below 18-20 psig.
- Fill the boiler and bleed all air from it.
- Check every boiler opening and pipe connection for leaks before fitting insulation.
- Check that no leaks exist on connections that will be covered by insulation.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
More commissioning tips for boiler
Source: Vitocrossal 200 CI2 Installation Instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.