Commissioning: Boiler tips (part 7 of 21)
Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.
Clearances to combustibles and top clearance
Viessmann · All Vitodens 100-W B1HE/B1KE models
The boiler is listed for zero clearance to combustibles when vented with listed AL-29-4C special venting or UL/ULC-listed CPVC gas vent. The top clearance is 12 in. (30 cm). Vent pipe clearances are in the Vitodens Venting System instructions.
- Keep 12 in. (30 cm) above the boiler.
- Use only the listed venting materials to get zero clearance to combustibles.
Clearances to hot water piping
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Keep a minimum 2 in. (51 mm) circumferential clearance from non-insulated hot water pipes to combustible construction. With suitable pipe insulation, the clearance may be reduced to 0 in. per local gas codes. Pumps in the piping examples are field supplied.
- Keep at least 2 in. (51 mm) around non-insulated hot water pipes from combustible construction.
- If pipes are insulated to appropriate thickness, the clearance may be reduced to 0 in. per local gas codes.
Closed-end connectors on red, orange and blue wires
Viessmann · Vitotronic burner wiring harness
The red, orange and blue wires have factory closed-end connectors. Red is live at 120VAC at all times.
- Do not remove or cut the closed-end connectors on the red, orange or blue wires unless it is necessary.
- Disconnect power before working on the red wire.
CO2 check before and after gas work
Viessmann · Vitocrossal 300 CA3B 2.5 to 6.0
Measure CO2 before and after any work on gas appliances to protect health and confirm correct condition.
- Measure CO2 before starting work.
- Measure CO2 again after the work is finished.
- Verify burner adjustment with the boiler at operating temperature.
Coding addresses auto-set for DHW and extra mixing circuits
Viessmann · Vitotronic 200-H HK3S (and HK1S for DHW tank systems)
With a DHW tank, and with extra mixing valve circuits on the HK3S, coding addresses 00:2 to 00:10 are set automatically.
Coding addresses set automatically when a DHW tank is used
Viessmann · Vitotronic 200-H HK1B, systems with a DHW tank
In systems with a DHW tank, coding addresses 00:2 to 00:10 are set automatically by the control unit.
Cold fill pressure and boiler filling
Viessmann · Vitocrossal 200 CI2 399 to 2000
Cold water fill pressure must match the expansion tank pressure. Do not let the cold fill pressure go above 18-20 psig. Fill only with suitable water, because poor water quality can damage the boiler.
- Set cold water fill pressure equal to the expansion tank pressure.
- Keep cold fill pressure at or below 18-20 psig.
- Fill the boiler and bleed all air from it.
- Check every boiler opening and pipe connection for leaks before fitting insulation.
- Check that no leaks exist on connections that will be covered by insulation.
Combustion air cover and room air operation
Viessmann · Concentric vent installations
The combustion air cover is not fitted at the factory on the concentric vent adaptor but ships with the boiler. Leaving it off can cause unintended room air dependent operation.
- Check the chosen venting configuration.
- Install the combustion air cover if the configuration requires it.
- For room air dependent operation, provide combustion and ventilation air per the single pipe venting section of the venting instructions.
Combustion chamber insert and door bolts
Viessmann · Vitorond 100 VR1 boilers
The boiler has a stainless steel combustion chamber insert. The door bolts must be tight before the burner is installed.
- Check that the combustion chamber door bolts are tight.
- Install the burner only after the door bolts are tightened.
Combustion test basis
Viessmann · Vitorond 200 VD2A, oil and gas combustion checks
Combustion efficiency and flue temperature figures assume a set CO2 level for each fuel, so set the burner to match the reference when comparing results.
- For fuel oil #2, reference CO2 is 13.0%.
- For natural gas, reference CO2 is 10%.
- Measure flue gas temperature with combustion air at 68 °F (20 °C) and boiler water at 176 °F (80 °C).
Commissioning and service test value record
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
Blank record sheet for combustion and gas readings, kept separately for Section 1, 2 and 3 on natural gas and LPG. Fields are static pressure, running supply pressure, CO2 and O2 (actual and set) at upper and lower rated output, CO (actual and set), flue gas temperature (gross), ionization current at upper and lower output, and draught.
- Record static pressure for each section, NG and LPG.
- Record running supply pressure for each section, NG and LPG.
- Measure CO2 at the upper rated heating output, then the lower rated output. Enter actual and set values.
- Measure O2 at the upper rated heating output, then the lower rated output. Enter actual and set values.
- Record CO (ppm) actual and set.
- Record gross flue gas temperature actual and set.
- Record ionization current in µA at the upper and lower rated heating outputs.
- Record draught actual and set (hPa / in. w.c.).
- Record results in the Maintenance Record at each service visit.
Commissioning hand-over checklist
Viessmann · All Vitocrossal 200 CM2 units
Initial start-up must be done by a qualified heating contractor, and the Maintenance Record must be completed.
- Verify field-supplied controls: low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents and thermostats.
- Explain the operating sequence and the need for combustion air to the owner.
- Demonstrate emergency shut-down, including what to do and what not to do.
- Tell the owner that annual professional service is required before the heating season.
- Leave all literature at the site and tell the owner where it is kept.
Common supply temperature sensor location
Viessmann · Single and multi-boiler systems
The mounting point depends on the system layout.
- For a single boiler, or multi-boiler with external cascade control, mount the common supply sensor on the supply piping near the boiler.
- For multi-boiler systems using integrated cascade, mount it on the supply piping common to all boilers.
- See the system layouts on page 45 of the manual.
Common venting and side wall coaxial venting
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Models 45, 57, 160 and 199 can only be common vented with other Vitodens 200-W boilers of the same size and series. Do not exceed the maximum equivalent vent length in the Venting System instructions. A side wall coaxial vent must include the Viessmann protective screen.
- Confirm the other boilers on the common vent are Vitodens 200-W of the same size and series.
- Check the total equivalent vent length against the Venting System instructions.
- Fit the Viessmann protective screen on any side wall coaxial vent.
Complete the setup wizard first
Viessmann · Multi-boiler cascade systems
The setup wizard for the boilers and the cascade control must be completed before any other configuration.
- Run the setup wizard on each boiler.
- Run the setup wizard on the cascade control.
- Start the additional configurations only after both wizards are complete.
Condensate pump and discharge location
Viessmann · Vitodens 200-W B2HA 80-100, 285-352
If the condensate outlet is lower than the drain, install a pump approved for condensing boilers with an overflow switch. The drain must end in an open or vented drain as close to the boiler as possible to prevent siphoning. Vent the tubing to atmosphere before a neutralization unit.
- Install a condensing-approved pump with an overflow switch if the outlet is below the drain.
- Terminate the drain into an open or vented drain close to the boiler.
- Vent the discharge tubing to atmosphere before the neutralization unit, if used.
- Vent the pipe between the siphon trap and the neutralization unit.
Conditions that prohibit burner start
Viessmann · Oil burner start-up
Do not attempt to start the burner in these conditions.
- Do not start the burner unless the combustion chamber door is secured in place.
- Do not start the burner if excess oil has built up, the unit is full of vapor, or the combustion chamber is very hot.
- Do not fire the boiler without water.
- Do not use gasoline, crankcase draining or any oil containing gasoline.
Configure BACnet IP device settings and activate
Viessmann · Versatronik 515 NR2/BACIP and 515D NR2/BACIP gateways
Set the BACnet device settings for the site network. Device ID must be unique on the whole BACnet internetwork. Changes do not take effect until the configuration is activated.
- Open the BACnet Device Settings screen.
- Enter a Device ID that is unique on the entire BACnet internetwork.
- Press SAVE on every screen where you change a setting.
- Select Activate Configuration and confirm the save. The gateway stores the settings and reboots automatically.
- Keep a record of every change made, because the gateway only shows configuration pages.
- Once the IP address is set, the gateway can join the network. Make sure no other device uses the same IP address.
Confirm burner cycling before leaving site
Viessmann · All Vitorond 100 VR1 installations
Check that the burner cycles on and off with a proper call for heat before leaving. Failure can cause a boiler runaway, which can lead to property damage, injury or death.
- Raise and lower the thermostat demand and confirm the burner starts and stops.
- Confirm the field-supplied high limit is set correctly before handover.
Confirm gas type before start-up
Viessmann · Gas type verification
The boiler is factory set for natural gas. Check the rating plate fuel type matches the installation and record it in the maintenance record on page 105.
- Compare the fuel type on the rating plate with the gas supplied.
- Record the fuel type in the maintenance record on page 105.
Confirm multi-boiler wiring before power-up
Viessmann · Combustion air devices and external controls
Disconnect power before wiring combustion air devices and external contacts. Use the adaptor and interface manuals for detailed installation.
- Disconnect power to control and burners before any wiring on these pages.
- Read the adaptor or common interface manual before installing the hardware.
Connect boiler control to LON system
Viessmann · Single boiler with Vitotronic 200-H, HK1B mixing valve control and Vitocom LON module
Set LON participant numbers and functions using coding level 2 and the LON table. Data transfer can take several minutes.
- Install the LON communication module (accessory) per its installation instructions.
- Set participant numbers: boiler control 1 (code 77:1), Vitotronic 200-H HK1B 10 (code 77:10), next unit 11 (set code 77:11).
- Make only one Vitotronic the fault manager (code 79:1); other units use code 79:0.
- Set time and outside temperature sharing codes per the LON table (7B:1, 81:3, 97:2, 97:1).
- Set LON participant fault monitoring to code 9C:20 on the units listed.
- Do not allocate the same participant number twice in one LON system.
Connect boiler to ViGuide Web
Viessmann · Vitocrossal 200 CI2 with ViGuide
Remote connection needs a Partner Account, and the system operator's email must be known. The connection ends if the system is not confirmed within 30 days.
- Turn on Internet > Accesspoint > On in settings (see the access label on the programming unit).
- Log in to the ViGuide app with a Partner Account and select Connect system.
- Select the boiler and follow the app steps.
- Confirm the connection in ViGuide Web within 30 days using the email sent to the system operator.
Connect the control unit to WiFi for app access
Viessmann · WiFi and app connection
Sets up remote access through the app. The WiFi credentials are on a label on the unit.
- Call up the home screen.
- Press and hold OK for about 4 sec until information is shown.
- Follow the instructions in the app.
- Confirm with OK at the end.
- Acknowledge the information with OK.
- Press and hold the exit button for about 4 sec to leave the menu.
Connect the gateway to the boiler control
Viessmann · Versatronik 511 with Vitotronic 100 GC1/GC1B, 300 GW2 or 300 GW5B
The supplied 3 ft (91 cm) CAT-5 cable joins the boiler control to the gateway. The control must have its LON communication card installed. Check the control's own manual for card location.
- Confirm the LON communication card is installed in the boiler control.
- Plug one RJ45 end of the supplied CAT-5 cable into the control.
- Plug the other RJ45 end into the RJ45 socket inside the gateway.
- Wire the BMS LON 2-wire bus to terminals A and B.
- Connect the 120VAC plug-in power cord (120VAC unit).
Connecting several remote controls
Viessmann · Multiple Vitotrol remote controls on one control unit
With more than one remote control, use the KM-BUS Expansion Module (accessory, Part No. 7133 393) or a field-supplied junction box. If only remote controls are on the bus, plug each one into the KM-BUS Expansion Module. If other KM-BUS participants are present, wire everything through a junction box. Total cable length must not exceed 50 m (164 ft).
- Use the KM-BUS Expansion Module (Part No. 7133 393) or a field-supplied junction box.
- If only remote controls are connected, plug each one into the KM-BUS Expansion Module.
- If other KM-BUS participants are connected, wire all devices through the junction box.
- Keep total cable length at or below 50 m (164 ft).
Connecting the control to the gateway
Viessmann · Vitotronic 300 GW5B, GW6B and 300-K MW2C controls
The supplied 3 ft (91 cm) CAT-5 cable links the boiler control LON card to the gateway RJ45 socket. The BACnet IP RJ45 connection goes into the gateway for the building network. The LON card must be installed in the control first, following the boiler control manual.
- Confirm the LON communication card is installed in the boiler control.
- Plug one end of the supplied CAT-5 cable into the control RJ45.
- Plug the other end into the RJ45 socket inside the gateway.
- Plug the BACnet IP RJ45 communication cable into the gateway.
Connecting the gateway to the boiler control
Viessmann · Versatronik 502 and 502D with Vitotronic 100/GC1, 300/GW2, 300-K and similar controls
The boiler control needs its LON communication card fitted. The gateway connects to the control with a supplied CAT-5 cable, with an RJ45 plug at each end. For full control-side setup, refer to the manual for the specific boiler control.
- Confirm the LON communication card is installed in the boiler control.
- Plug one RJ45 end of the supplied 3 ft (91 cm) CAT-5 cable into the control.
- Plug the other RJ45 end into the RJ45 socket inside the gateway.
- For 120VAC units, plug in the supplied power cord.
Connection points on the DIN-rail gateway
Viessmann · Versatronik 511D NR2/LON
The 511D has four labelled connection points: the control RJ45 port, the paralleled BUS connection, the LON terminals A and B, and the 24VAC power input.
- Connect the control RJ45 port to the boiler control.
- Use the paralleled BUS connection where needed.
- Connect the LON field wiring to terminals A and B.
- Connect 24VAC power.
Control connections and cable routing
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Cabling is needed for the outdoor sensor, Vitotronic 200-H HK1B, the mixing valve kit, remote operating mode switching, remote disable, alarm output, wall-mount base and circulating pump. Only one accessory or switch contact can be connected to a plug contact at a time.
- Route the cables as illustrated so the control unit can move freely.
- Do not secure connecting cables to the control unit bracket.
- Keep cable runs within the maximum permitted cable temperatures.
- Connect accessory power at the control; it switches with the system on/off switch.
- Supply the Vitotronic 200-H HK1B, mixing valve kit and Solartrol from a separate 120 VAC wall receptacle.
- Insert the programming unit into the control unit support, or use a wall mounting base (accessory) near the boiler.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.