Carrier Heat Pump: How to read the heating performance grids
How to read the heating performance grids on a Carrier heat pump: Find the airflow block that matches the indoor unit airflow in CFM, then go down to the outdoor dry bulb temperature. Read across to the indoor dry bulb column for capacity (BTU/hr) and power input (kW). Pick the nearest indoor condition column for the room being checked.
Applies to: D5CURA + D5FUAA heating performance
How to fix how to read the heating performance grids: step by step
- Select the table for the unit size (Tables 14 to 17 on these pages).
- Choose the airflow block nearest the actual CFM.
- Find the outdoor dry bulb row (-13°F to 75.2°F).
- Read TC (BTU/hr) and PI (kW) for the indoor dry bulb column that matches the room condition.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: D5CURA Product Data, p. 40-47. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.