Viessmann Heat Pump: Refrigerant pipe burial limits
Refrigerant pipe burial limits on a Viessmann heat pump: Do not bury more than 36 in. (914 mm) of refrigerant pipe. If any section is buried, it needs a 6 in. (152 mm) vertical rise to the outdoor unit valve connections. Longer buried runs let refrigerant migrate to the cold section during shutdown, which can cause slugging and compressor damage at start-up.
Applies to: DLCLRC sizes 36K-58K refrigerant piping
How to fix refrigerant pipe burial limits: step by step
- Limit buried refrigerant pipe to 36 in. (914 mm).
- Provide a 6 in. (152 mm) vertical rise to the outdoor valve connections where any pipe is buried.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Viessmann DLCLRC service manual, p. 2 of 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.