Carrier Heat Pump: Test DC voltage between communication ports and reactor resistance
Test DC voltage between communication ports and reactor resistance on a Carrier heat pump: Used to tell a normal communication signal from a fault on the outdoor or indoor side.
Applies to: Outdoor unit communication circuit
How to fix test dc voltage between communication ports and reactor resistance: step by step
- Set the multimeter to DC voltage.
- Connect the red lead to the 2 port (or S or L2 port) and the black lead to the 3 port (or N or S port) of the outdoor unit.
- With the AC running normally, the voltage swings between positive and negative values.
- If the voltage is always positive, suspect the outdoor unit.
- If the voltage stays at one fixed value, suspect the indoor unit.
- To check the reactor, disconnect it from the capacitor and measure its resistance. A normal reading is close to zero ohms. Replace the reactor if it is not.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
Source: D5FCFAH service manual, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.