Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Carrier Heat Pump: RS485 communication error between indoor and outdoor unit

Updated · by Aurora Star Tech Inc.

RS485 communication error between indoor and outdoor unit on a Carrier heat pump: The indoor unit cannot communicate with the outdoor unit over the RS485 line. No specific code is shown on these pages.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Indoor and outdoor unit RS485 communication

Common causes of rs485 communication error between indoor and outdoor unit

  • Interference from nearby lamps, power transformers, or a long signal wire
  • Signal wire not shielded or shield not earthed
  • Broken signal wire
  • Signal wires not seated properly on the PCB
  • Faulty indoor or outdoor main PCB

How to fix rs485 communication error between indoor and outdoor unit: step by step

  1. Turn the power off, then restart the unit 2 minutes later.
  2. Check whether the signal wire is shielded and whether the shield is earthed. Use shielded cable with the shield earthed.
  3. Check for interference such as many lamps or power transformers, or a signal wire that is too long. Remove the interference or add a magnetic ring on the power wire.
  4. Check that the signal wire is not broken and replace it if it is.
  5. Check that the signal wires are fully seated on the PCB. Pull them out and reinsert them.
  6. Replace the indoor main PCB and check whether the error clears.
  7. If the error remains, replace the outdoor main PCB.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Heat Pump codes

Models

37MAHAQ37MARAQ37MGHAQ37MGRAQ

Source: D5FCFAH service manual, p. 35. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977