Carrier Heat Pump: Defrost mode entry and exit
Defrost mode entry and exit on a Carrier heat pump: Defrost starts when any entry condition is met and ends when a defrost end condition is met. Symbols TCDI1, TCDI2, TCDI3, TCDE1 and TCDE2 are not defined on these pages, so use the values in the controller data.
Applies to: D5FCFAH
Common causes of defrost mode entry and exit
- Frost build-up on the outdoor coil in heating
- Outdoor coil temperature T3 falls below defrost thresholds
How to fix defrost mode entry and exit: step by step
- Record the minimum T3 from minute 10 to minute 15 after compressor start (T30).
- Expect defrost after 29 min if T3 is below TCDI1 and T3 plus the SUB offset is at or below T30.
- Expect defrost after 35 min if T3 is below TCDI2 and T3 plus the SUB offset is at or below T30.
- Expect defrost after 29 min if T3 stays below TCDI3 for 3 minutes.
- Expect defrost after 120 min if T3 is below 5°F (-15°C).
- End defrost when T3 rises above TCDE1, or stays above TCDE2 for 80 seconds, or defrost has run 10 minutes.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
Source: D5FCFAH service manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.