Updated · by Aurora Star Tech Inc.

Replay or clear the last five faults (RGPE/RGLE) on a Rheem furnace: On a power reset the dual display plays back the last five faults, newest first. Codes 82, 11, 45, 46 and 57 are not stored twice in a row.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Rheem/Ruud RGPE / RGLE modulating furnaces

How to fix replay or clear the last five faults (rgpe/rgle): step by step

  1. Cycle power to the furnace control
  2. Watch the display: the last five faults appear, newest first
  3. To clear, flip DIP switch SW3-2 four times in a row, alternating, within 30 seconds, then return it to its original position; or use CLEAR FAULTS in the thermostat menu
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

RGLE-05(-)BMKRRGLE-07(-)AMKRRGLE-07(-)BRQRRGLE-10(-)BRMRRGLE-12(-)ARMRRGPE-05(-)BMKRRGPE-07(-)AMKRRGPE-07(-)BRQRRGPE-10(-)BRMRRGPE-12(-)ARMR

Source: RGPE Fault Code Buffer, p.49. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.