Settings shortcuts: Boiler tips (part 10 of 10)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on settings shortcuts for boiler. Check each one against the manual for your exact model before acting.

Switching off DHW heating

Viessmann · Vitocrossal 300 CA3B

DHW heating can be turned off by setting the DHW temperature to its minimum.

  1. From the home screen, select DHW temperature setpoint.
  2. Use the controls to set 50°F (10°C).
  3. Confirm.

Turn automatic summer/wintertime changeover on or off

Viessmann · Control panel

Sets whether the control changes time automatically between summer and winter time.

  1. Open Settings, then 'Date and time'.
  2. Select 'Time changeover'.
  3. Select 'ON' or 'OFF'.
  4. Confirm.

Turn off DHW heating but keep central heating

Viessmann · Vitocrossal 300 CU3A

Set the DHW temperature to the lowest value to stop DHW heating while the heating circuit still runs. The manual gives 50°F (10°C) for this.

  1. Open the extended menu.
  2. Select 'Heating'.
  3. Select the heating circuit.
  4. Select 'Heating program' and choose 'Heating and DHW'.
  5. Open 'DHW'.
  6. Select 'Set DHW temperature'.
  7. Set the value to 50°F (10°C).

Turn on comfort mode for a heating circuit

Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Starts comfort mode for one heating circuit and sets the room temperature target used during comfort mode. Settings can be changed only at the system and lead control boiler section 1.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit (1, 2 or 3).
  3. Open Comfort mode and select Comfort mode again.
  4. Press OK to confirm.
  5. Select the required comfort mode room temperature target.
  6. Press OK to confirm.

Turn on economy mode for a heating circuit

Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Energy saving function. It can only be enabled while the system is in standard heating mode. Settings can be changed only at the system and lead control boiler section 1.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Economy mode and select Economy mode again.
  4. Press OK to confirm.

Use energy saving mode

Viessmann · Vitotrol 300 remote control

Only available in the heating operating mode. The room temperature is automatically lowered. The mode ends at the next automatic switch to reduced room temperature, or it can be cancelled early.

  1. Press the energy saving key; the key lights and the icon shows briefly.
  2. To end early, press the key again; the light goes off.

Use Extended heating during a reduced time phase

Viessmann · Heating circuits with time programs

Keeps the rooms at the last active standard or comfort temperature during a reduced phase. It ends automatically at the next standard or comfort phase, or can be ended early.

  1. Select the heating circuit in the menu bar if applicable.
  2. Tap the Extended heating button to switch it on.
  3. To end early, select the heating circuit and tap the button again.

View the heating cycles on the time line

Viessmann · Vitotrol 300 remote control

The selected cycles are shown on a time line, for all days or for a single day.

  1. Open the flip-down cover of the remote control.
  2. Press the two overview keys together; the cycles for the day appear on the time line.
  3. Close the cover.

Water temperature range from the control panel

Viessmann · Vitotron 100 VLN2

The boiler is preset for radiant floor, radiant ceiling, hot water baseboard and water to air applications. Temperatures can be set between 85°F and 140°F.

  1. Set the desired water temperature on the control panel within 85°F to 140°F.
  2. Choose a setting that matches the application (radiant floor, radiant ceiling, baseboard or water to air).

Where the fault history lives

Viessmann · Vitodens 200-W B2HE 85, 120, 150, 199

The message history keeps the 10 most recent faults with their subscriber numbers (CAN 1 HMU, CAN 50 BCU, CAN 59 HMI, CAN 60 fan, 81 MZIO).

  1. Service menu > Message history

0-10VDC remote modulation input setup and operation

Weil-McLain · Single boiler remote modulation

Remote modulation works only on a single boiler, not one in a network. It replaces the INPUT 1 heat demand, and the control cannot use both 0-10VDC target and modulation.

  1. Set up the boiler as a single boiler in the Unity control.
  2. Connect the signal positive to terminal 6 and common to terminal 5 on P15.
  3. Assign INPUT 1 to PRIORITY 2 during the WIZARD.
  4. In the ASSIGN INPUTS menu for INPUT 1, change SOURCE from TT1 to 0-10V.
  5. Expect a heat demand at 0.9 VDC, which turns off at 0.8 VDC.
  6. 2 VDC equals 10% input and 10 VDC equals 100% input. These voltage points are fixed.
  7. OUTPUT 1 energizes with the heat demand and can drive the system pump.

Change fuel type in Boiler Settings

Weil-McLain · ECO Tec control

The control shows Fuel Type under Boiler Settings. It must match the gas the boiler is running on.

  1. Open the Contractor menu, then Boiler Settings.
  2. Select Fuel Type and set it to Propane or Natural Gas to match the installed venturi and orifice.

Check the control date and time

Weil-McLain · Evergreen Pro control on Series 2 boilers

Confirm the date and time on the control so faults are logged correctly. Check it from the Date/Time screen under the Menu. If wrong, change it in the USER MENU.

  1. From the Home screen, swipe to the Menu screen.
  2. Select Date/time and read the displayed date and time.
  3. If incorrect, open the USER MENU and change the date and/or time.

Control display navigation gestures

Weil-McLain · ECO Tec control, all wizard and menu screens

The ECO Tec control uses a touch screen. Swipe moves forward and back between screens. Press touches an icon to act. Scroll is done by holding a finger on the empty part of the slide bar, or by swiping up or down. Double tap a editable parameter to enter edit mode.

  1. Swipe left or right to move between screens.
  2. Press the icon on screen to carry out the action shown.
  3. To scroll, hold a finger on the empty part of the slide bar, or swipe up or down.
  4. Double tap an editable parameter to open it for editing.

DHW priority settings on zone valve systems

Weil-McLain · Zone valve DHW tank

Priority 1 is the default for DHW and turns off lower priorities during DHW calls. Max on time can limit this.

  1. Keep Priority 1 for DHW if DHW should take precedence.
  2. Use Priority 2 or 3 for DHW if priority is not wanted.
  3. Set max on time to limit how long DHW priority runs.
  4. Avoid overriding Outdoor Reset to DHW mode when the system is for space heating; this may violate Section 303 of the 2007 Energy Act.

Disable FREEZE PROTECT when not used

Weil-McLain · All EG / PEG Series 7 boilers

If freeze protection or circulator exercising is not used, FREEZE PROTECT must be turned off in the Advanced Menu.

  1. Open the Advanced Menu.
  2. Go to the CIRCULATOR settings.
  3. Set FREEZE PROTECT to disabled.

Hot water menu shortcuts

Weil-McLain · Combi models

The homeowner HOT WATER menu controls combi hot water temperature and the preheat and ECO Boost modes.

  1. Open MENU and select HOT WATER.
  2. Edit the hot water temperature for the combi demand.
  3. Enable or disable PREHEAT mode or ECO BOOST as needed.

Reset maintenance reminder

Weil-McLain · ECO Tec Series 3 80/110/150/199

The display shows a maintenance reminder (default 12 months). The contractor resets it after service.

  1. Open the SERVICE menu and go to Service Info.
  2. Select RESET REMINDER to update the last maintenance date and next due date.
  3. Homeowner can use reset to only update the next due date.

Set date, time and auto DST

Weil-McLain · ECO Tec control date and time setup

The date and time are set with slide wheels. Accurate time matters for maintenance intervals and troubleshooting records.

  1. Select DATE/TIME from the boiler settings screen.
  2. Set the date with the slide wheels, then press the blue TIME button.
  3. Set the time with the slide wheels; press the blue AM/PM button to change AM or PM.
  4. Check the AUTO DST box so the control changes time for daylight saving.
  5. Press the back arrow when done, then confirm all settings and press the right arrow.

Set the date and time

Weil-McLain · Date and time setup

Date and time feed the maintenance timing and the lockout history time stamps.

  1. Open the Set Time and Date menu.
  2. Set year, month, day, hour and minute.
  3. Confirm the display shows the correct time.

Set up 0-10VDC remote target input

Weil-McLain · Remote target input in PRIORITY SETTINGS

A 0-10VDC signal adjusts the supply target temperature through the TARGET ADJUST setting. The control interpolates the target between the set voltage and temperature points.

  1. Use PRIORITY 1 for DHW if used, and verify its settings.
  2. Use PRIORITY 2 for heating and set TARGET ADJUST to 0-10V.
  3. Set VOLTS FOR MAX to the voltage that calls for the highest target, and set SUPPLY MAX to that temperature.
  4. Set VOLTS FOR MIN to the voltage that calls for the lowest target, and set SUPPLY MIN to that temperature.
  5. Connect the signal positive to P15 terminal 6 and common to terminal 5.
  6. A dry contact heat demand must still be wired to an input to start a call for heat.

Touch screen navigation

Weil-McLain · ECO Tec Series 3 control display

The display uses swipe, press, scroll and double-tap. A keyboard appears only when editing input/output names or contractor information.

  1. Swipe left or right to move between screens.
  2. Press an icon to perform its action.
  3. To scroll, press and hold on the empty part of the slide bar, or swipe up or down on applicable screens.
  4. To edit a parameter, double-tap it to enter edit mode.

Wizard help and input locator

Weil-McLain · ECO Tec Control wizard

Each wizard step has HELP and WHERE buttons. WHERE shows a control diagram and the location of the input and output being set.

  1. Press HELP for an explanation of the selected line.
  2. Press WHERE on any input/output screen to find the matching input and output on the control diagram.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.