Reset & cancel: Boiler tips (part 8 of 8)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on reset & cancel for boiler. Check each one against the manual for your exact model before acting.

Clear all history counters

Weil-McLain · ECO Tec Series 3 boilers

Pressing reset in the fault history menu deletes all history, not just the counter you are viewing. To keep history, clear counters one at a time instead.

  1. Open the FAULT HISTORY menu.
  2. To clear everything, press the reset button. This deletes all history.
  3. To keep history, select each counter (for example Ignition Retries) and reset only that one.

Clear all lockout histories

Weil-McLain · ECO Tec Series 3 control display

Erases the recorded lockout history.

  1. On the FAULT HISTORY screen, hold the reset button until the history is cleared.

Clear an ignition lockout

Weil-McLain · SVF 1500-3000

After an ignition lockout, the display turns red. Clear it from the Diagnostic Menu.

  1. Open the Diagnostic Menu.
  2. Select Manual Reset.
  3. Open the manual gas valve if it was closed.

Manual reset after lockout

Weil-McLain · Ultra U-Control manual reset lockout

A high limit lockout or a manual reset limit lockout requires a manual reset. The reset is done from the control and can be done by a homeowner or service technician.

  1. Find the cause of the lockout first.
  2. Enter the MANUAL RESET menu.
  3. Press ENTER to reset the listed errors.
  4. Confirm the boiler restarts normally.

Manual reset of an ignition lockout

Weil-McLain · EG / PEG Series 7 boilers with Unity-CI control

An ignition fault must be reset by hand from the fault screen. The fault clears only if the underlying condition has been corrected.

  1. Go to the fault indication screen.
  2. Press and release the enter button. A confirmation screen appears.
  3. Answer Yes and press and release enter to clear the fault, but only after the cause is fixed.

Manual reset procedure for ignition lockout

Weil-McLain · EG and PEG Series 7 water boilers

Use this procedure to clear a manual reset lockout caused by an ignition fault.

  1. Make sure the ignition fault has been corrected first.
  2. On the fault indication screen, press and release the enter button to open the confirmation screen.
  3. The reset question shows NO on line 2. Press enter to change it.
  4. Press the up or down arrow to change the answer to YES, then press enter again.
  5. The display background turns green and returns to the main screen.

Reset a boiler lockout at the U-Control display

Weil-McLain · Ultra Series 4 boiler with U-Control display

When the boiler locks out, the U-Control display turns red.

  1. Check the U-Control display. A red display means the boiler has locked out.
  2. Select MANUAL RESET on the U-Control display to reset the boiler (shown in Figure 4, page 10).

Reset all history counters

Weil-McLain · Evergreen Pro Series 2 boilers

Clears all boiler history at once. Deletes every history record, so only use it when the full history is no longer needed.

  1. Open the DIAGNOSTICS menu and go to Fault History.
  2. Press the reset button.
  3. To keep some history, reset the individual counters instead.

Reset all history counters to zero

Weil-McLain · ECO Tec Series 3 80/110/150/199

Deletes all history. To keep history, reset counters one at a time.

  1. Enter the FAULT HISTORY menu.
  2. Press the reset button. All history is deleted.

Reset control to factory default

Weil-McLain · SVF 1500-3000 Series 1 boiler

Restores all control settings to the factory values. Previous settings cannot be recovered.

  1. Go to the BOILER SETTINGS menu (see page 75).
  2. Select Reset to Factory Default.
  3. Hold Enter for the specified time to confirm.
  4. Confirm this is really wanted before continuing, since previous settings are lost.

Reset error counters

Weil-McLain · Ultra 80, 105, 155, 230, 299, 399

ERRORS screen counts: control faults, ignition retries (shows current sequence), manual reset count and auto reset count.

  1. Go to DIAGNOSTICS > ERRORS.
  2. Select the Control Fault count or the Manual Reset / Auto Reset count and press enter to reset it.

Reset ignition retries at yearly maintenance

Weil-McLain · Evergreen Pro Series 2 boilers

The ignition retry count is cumulative. The manual recommends resetting it during yearly service.

  1. Open DIAGNOSTICS > Fault History.
  2. Select Ignition Retries.
  3. Press the Reset button.

Reset ignition retries counter at yearly service

Weil-McLain · SVF 1500, 2000, 2500, 3000

The manual recommends resetting the ignition retries counter during yearly maintenance so the new count starts from zero.

  1. Open DIAGNOSTICS and go to PAST ERRORS, then IGNITION RETRIES.
  2. Either hold the left and right arrows, or select the IGNITION RETRIES line and press Enter.

Reset ignition retry count

Weil-McLain · ECO Tec Series 3 control display

Ignition retries should be reset during yearly maintenance.

  1. On the FAULT HISTORY screen, select the Ignition Retries parameter and press enter to reset the count.
  2. Or press the reset button to reset the count.

Reset pressure switch fault

Weil-McLain · CGi and LGB Series 3 boilers with pressure switch

Pressure switch cuts off gas flow when the vent system is blocked. Reset only after the blockage is cleared.

  1. Resolve the cause of the fault first
  2. Press Enter (square symbol)
  3. Use the arrow keys to select YES
  4. Confirm the error screen returns to the default display
  5. If the fault returns, contact a service technician

Reset the maintenance reminder

Weil-McLain · Evergreen Pro control display

When maintenance is due, a wrench icon shows on the main screen. A qualified technician should inspect the boiler first. Maintenance intervals should be set by a qualified technician at installation.

  1. Open the User Menu and select Maintenance to view contractor and maintenance information.
  2. After the technician inspection, reset the maintenance reminder to clear it.

Reset to factory default

Weil-McLain · ECO Tec Series 3 control

Returns control settings to factory values. Previous settings cannot be recovered.

  1. Hold the button for the specified time, or use Contractor Menu, Boiler Settings, Reset Factory Default.
  2. On 199 and 199C models, select the correct blower motor after checking the blower label (see page 115).
  3. Confirm this action is really needed before continuing.

Restart the Wizard after it was bypassed

Weil-McLain · Evergreen Series 2 control

If the Wizard was skipped by mistake, the boiler setup must be started over from the beginning.

  1. Go to the Boiler Settings menu.
  2. Select RESET FACTORY DEFAULTS.
  3. Select RESTART Wizard and follow the screens.

Restart the wizard or reset to factory defaults

Weil-McLain · Evergreen Series 2 with Evergreen Pro control

The Restart Wizard option keeps contractor data. Reset Factory Defaults clears everything, including the model number.

  1. Open BOILER SETTINGS from the contractor menus and select RESET FACTORY DEFAULTS.
  2. Choose RESTART WIZARD to keep contractor information, time and date, run times, errors and boiler model, then run the wizard again.
  3. Choose RESET FACTORY DEFAULTS only if you need to clear all information and return the control to its as-shipped state. The model must be set again.

Restart Wizard

Weil-McLain · ECO Tec Series 3 control

Erases user-specific settings and takes the user back through the wizard. Previous settings cannot be recovered.

  1. Hold the button for the specified time.
  2. Confirm this action is really needed before continuing.

Review lockout history

Weil-McLain · Ultra Series 4 boilers, U-Control

The U-Control stores the last three lockouts with time, status and detail menus. Use them to see what happened before the lockout.

  1. Open Errors and select Lockout History 1 for the most recent lockout.
  2. Check Time and Date and Status to see the boiler state at the time of the lockout.
  3. Open Manual Reset or Auto Reset to see the detail for that lockout type.
  4. Open Inputs, Outputs or Temperatures to see the state at the time of the error.
  5. Repeat for Lockout History 2 and 3.
  6. Manual Reset Cnt and Auto Reset Cnt show counts since last cleared.

Wizard use, skip and restart

Weil-McLain · ECO Tec Series 3 control setup

The setup wizard guides the install step by step and is recommended. Skipping it requires manual setup of every setting and is not recommended.

  1. Press USE WIZARD to run the guided setup. USE APP can load a settings file from the app.
  2. If you press SKIP WIZARD, the wizard can be restarted later from Reset to Factory Defaults in the Boiler Settings menu in the Contractor menu.
  3. If the boiler model shown does not match the installed model, perform a FACTORY RESET and select the correct model.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.