Viessmann Mini-Split: Buried refrigerant piping limits
Buried refrigerant piping limits on a Viessmann mini-split: Do not bury more than 36 in (914 mm) of refrigerant pipe. If any section is buried, it needs a 6 in (152 mm) vertical rise to the outdoor unit valve connections. Excess buried length can let refrigerant migrate to the cold section and cause slugging that may damage the compressor at start-up.
Applies to: DLFSHC refrigerant piping
How to fix buried refrigerant piping limits: step by step
- Limit buried refrigerant pipe to 36 in (914 mm) maximum.
- If any pipe is buried, provide a 6 in (152 mm) vertical rise to the outdoor valve connections.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
DLFSHCH06XAKDLFSHCH09XAKDLFSHCH12XAJDLFSHCH12XAKDLFSHCH18XAKDLFSHCH24XAKDLFSHCH30XAKDLFSHCH36XAK
More other tips for mini-split
Source: DLFSHC installation instructions, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.