Viessmann Heat Pump: Troubleshooting approach with the LED display
Troubleshooting approach with the LED display on a Viessmann heat pump: Start by checking the indoor unit code, then use the flow charts. Some problems have no code.
Applies to: DLCLRC indoor and outdoor units
How to fix troubleshooting approach with the led display: step by step
- Check the diagnostic code on the indoor unit first; the outdoor board LED shows only a few errors.
- If there is no code, use the diagnostic flow charts for the symptom.
- Disconnect main power before removing covers or boards.
- Power up again to measure the outdoor board inputs and outputs with a digital multimeter.
- Use the wiring diagrams for the measurement points.
- Some DC signals are pulsing; a pulse should move steadily when the signal is present.
- Disconnect main power before reinstalling any board.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Vitocal 100-S DLCLRC service instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.