Viessmann Heat Pump: Triple evacuation method
Triple evacuation method on a Viessmann heat pump: Repeated pull-down and dry nitrogen purge sequence used to remove moisture and contaminants from the system.
Applies to: DLCURA outdoor units
How to fix triple evacuation method: step by step
- Pump the system down to 500 microns and keep the pump running for an additional 15 minutes.
- Close the service valves and shut off the vacuum pump.
- Connect a nitrogen cylinder and regulator. Open until system pressure reads 2 psig.
- Close the service valve and let the system stand for 10 minutes so dry nitrogen can absorb moisture.
- Repeat the evacuation and purge cycle as shown in Fig. 16 until the system holds a deep vacuum.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCURA Service Manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.