Viessmann Heat Pump: S communication DC voltage check (indoor to outdoor link)

Updated · by Aurora Star Tech Inc.

S communication DC voltage check (indoor to outdoor link) on a Viessmann heat pump: Used when the indoor and outdoor units do not communicate. Measure DC voltage between the S terminal and the N or L2 terminal. The reading shows whether the signal and board are working.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DLCLRC outdoor units with indoor fan coil

Common causes of s communication dc voltage check (indoor to outdoor link)

  • Wiring fault between indoor and outdoor units
  • Short-circuited component on the main board
  • Faulty IPM board or main PCB
  • Faulty electronic expansion valve coil

How to fix s communication dc voltage check (indoor to outdoor link): step by step

  1. Power off, then restart the unit after 2 minutes.
  2. Measure DC voltage between N or L2 and S. Black probe to S, red probe to N or L2.
  3. If the reading is fixed and close to 0, the indoor unit is faulty.
  4. If the reading alternates between negative and positive, the link is working normally.
  5. If the reading is always positive, the outdoor unit is faulty.
  6. Check the wiring between indoor and outdoor units, and the wiring from the outdoor terminal to the outdoor PCB.
  7. Check the wiring from the indoor terminal to the indoor PCB.
  8. Turn the unit on and check whether W and 1(L) are connected. Check whether the power LED is on.
  9. Check the AC voltage of L and N output to the IPM board. It should match the power input.
  10. Check DC 5 V and 12 V from the IPM board to the main PCB.
  11. Unplug high voltage components on the main PCB one at a time (4-way valve, heater, AC fan) and check their resistance for a short circuit.
  12. Unplug the electronic expansion valve and check the DC 5 V and 12 V again.
  13. Replace any short-circuited component and the main PCB, or replace the IPM board, or replace the indoor PCB, as the checks indicate.
  14. If the expansion valve coil is faulty, replace the coil.
  15. NOTE: On some models the outdoor PCB cannot be removed separately. In that case replace the whole outdoor electric control box.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Source: DLCLRC Service Manual, p. 20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.