Viessmann Heat Pump: Replace electronic control board, PCB 18K (208/230V)
Replace electronic control board, PCB 18K (208/230V) on a Viessmann heat pump: Access and removal of the control board on the 18K model with 208/230V supply. Several sensor and valve connectors must be disconnected.
Applies to: DLCSRB 18K model, 208/230V
How to fix replace electronic control board, pcb 18k (208/230v): step by step
- Remove the screws and loosen the hooks, then open the electronic control box cover (5 screws and 2 hooks).
- Disconnect the fan motor connector from the electronic control board.
- Remove the compressor connector.
- Pull out the two blue wires connected to the four-way valve.
- Pull out the connectors of the condenser coil temperature sensor (T3), outdoor ambient temperature sensor (T4) and discharge temperature sensor (TP).
- Disconnect the electronic expansion valve wire.
- Remove the connector for the DR and reactor.
- Remove the electronic control board.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCSRB Service Manual, p. 71. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.