Viessmann Heat Pump: Remove compressor
Remove compressor on a Viessmann heat pump: Remove the panel plate and the PCB compressor connection before disassembling the sound blanket. Refrigerant recovery and the R32/R290 evacuation and nitrogen flush must be done first, as in the four-way valve procedure. Work should be done by an authorized technician.
Applies to: DLCSRB outdoor units
How to fix remove compressor: step by step
- Remove the terminal cover flange nut and take off the terminal cover.
- Disconnect the compressor connectors.
- Remove the hex nuts and washers that hold the compressor to the bottom plate.
- Heat the brazed joints and remove the discharge pipe and the suction pipe.
- Lift the compressor off the base pan with pliers.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Vitocal 100-S DLCSRB service manual, p. 77-78. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.