Updated · by Aurora Star Tech Inc.

Refrigerant line installation rules on a Viessmann heat pump: Limits for the interconnecting refrigerant lines between indoor and outdoor units. Standard charge covers 25 ft of line. Lines must be insulated and not buried deeper than allowed.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DLCURA outdoor units 18K to 60K

How to fix refrigerant line installation rules: step by step

  1. Keep each run at least 10 ft (3 m) between indoor and outdoor units.
  2. Charge is factory-set for runs up to 25 ft (7.6 m). Longer runs need extra refrigerant per the piping table.
  3. Do not bury lines. If a section must be buried, bury no more than 36 in (914 mm) and provide at least a 6 in (152 mm) vertical rise to the service valves.
  4. Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation. Use closed-cell insulation for long-line runs.
  5. Insulate both refrigerant lines separately.
  6. Isolate the tubing from the building structure so vibration and noise are not transmitted.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Source: DLCURA Service Manual, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.