Viessmann Heat Pump: Refrigerant circuit work: checks before starting
Refrigerant circuit work: checks before starting on a Viessmann heat pump: Checks needed before opening the refrigerant circuit so the risk of ignition is minimised.
Applies to: Vitocal 100-AW AM2V refrigerant circuit
How to fix refrigerant circuit work: checks before starting: step by step
- Switch off power to the indoor and outdoor units and confirm the system is dead; there may be more than one power circuit.
- Check the refrigerant circuit for leaks.
- Ventilate well, especially near the floor, and keep it ventilated for the whole job.
- Check the area around the heat pump for flammable material and ignition sources, and remove them.
- Check the surrounding air with a sparkless, sealed R32-suitable refrigerant detector before, during and after the work.
- Inform maintenance staff and people nearby about the work.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V installation manual, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.