Viessmann Heat Pump: Reactor resistance check and S-line measuring points
Reactor resistance check and S-line measuring points on a Viessmann heat pump: Use a multimeter to check the reactor with the capacitor disconnected. A good reactor reads around zero ohms; otherwise it has failed. For the S-line DC voltage test, the red probe goes to 2 (L2 or S) and the black probe goes to 3 (N or S). Normal running shows alternating positive and negative values. A constant positive value means an outdoor fault; no change means an indoor fault.
Applies to: Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK
How to fix reactor resistance check and s-line measuring points: step by step
- Disconnect the reactor from the capacitor and measure its resistance.
- Replace the reactor if the reading is not close to zero ohms.
- For the S-line test, connect the red probe to 2 (L2/S) and the black probe to 3 (N/S).
If the unit shows an error code, look it up: Viessmann Heat Pump codes
More service & test modes tips for heat pump
Source: Viessmann Vitocal IND-A DLFUAA service manual, p. 19-20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.