Service & test modes: Heat Pump tips (part 2 of 2)
Short, practical technician tips on service & test modes for heat pump. Check each one against the manual for your exact model before acting.
Force a defrost test (PRL-JEC)
Rheem · Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
With the unit running in heat-pump mode, SW2 forces a defrost that runs until the termination temperature is reached or 14 minutes pass.
- Set the thermostat to heat and make a heat call
- Press SW2 for one second with the unit running in heat-pump mode
- Watch the unit enter defrost; press SW2 again to stop the test early
Review or clear stored faults on the ICC display (PRL-JEC)
Rheem · Rheem/Ruud PRL-JEC heat pumps with Comfort Control2 ICC
Scrolls the stored fault history on the dual display, newest first; up to six are kept and 0 means none. The mode exits by itself after the last fault.
- Press TEST and SW2 together with insulated probes for one second and release
- Watch the display scroll through the faults, newest first
- To erase, hold TEST and SW2 together for five seconds and release; the top and bottom segments flash to confirm
Force a defrost cycle with the button
Trane · 5TWR7 multi-speed outdoor drive
Holding the forced defrost button on the control board starts a defrost; the display then shows 7 as the first digit (Defrosting). Not possible in cooling.
- Run the unit in heating mode with the thermostat calling
- Hold the forced defrost button on the control board down for over 5 seconds
- The display shows 7 as the first digit when forced defrost begins
Actuator test menu (code 45)
Viessmann · Indoor unit (IDU) service menu
Service menu function that runs the actuator test on the indoor unit (IDU). Requires an access code.
- Open the Service menu and select the actuator test.
- At the access code prompt, turn the navigation dial to 45 and press the dial to confirm.
- Scroll through the test list with the dial and press to select each test.
- When finished, select 'End' to return to the Service menu.
- To leave the code screen without entering a code, hold the dial or wait for the display to return to the main screen.
Forced defrost
Viessmann · DLCSRB units with remote control
Manually starts a defrost cycle for testing.
- Press and hold AUTO/COOL for 5 seconds to start forced defrost.
- The indoor fan stops and the defrost lamp lights.
- Use the remote to turn the unit off to end normal defrost.
- To leave forced defrost, press and hold AUTO/COOL for 5 seconds again.
Forced operation (TOUCH button)
Viessmann · DLCSRB indoor high-wall units
Runs the unit in forced auto or forced cooling without the remote. General protections and remote control stay active.
- With the unit off, press TOUCH once to start FORCED AUTO at 75.2°F (24°C).
- Press TOUCH again within 5 seconds to start FORCED COOLING.
- In FORCED COOLING the compressor runs at F2 and the fan runs at breeze speed for 30 minutes, then the unit goes to AUTO at 75.2°F (24°C).
- Press TOUCH to turn the unit off from any forced mode.
Heat pump module operating conditions (code 65)
Viessmann · Vitocal 100-AW AM2V
The Heat Pump Module menu shows heat pump operating conditions and the defrost parameters.
- Open the Heat Pump Module menu.
- When prompted, turn the navigation dial to code 65 and press to confirm.
- View the operating conditions.
- Choose End to return to the Service menu.
Heat pump operating conditions view (code 65)
Viessmann · Heat pump module (outdoor unit data)
Service/Configuration menu item that shows live heat pump operating conditions. Requires an access code.
- Open the Service/Configuration menu and select Heat Pump Module.
- At the access code prompt, turn the dial to 65 and press to confirm.
- Scroll through the readings with the dial and press to select.
- Select 'End' to return to the Service menu when done.
Indoor unit actuator test (code 45)
Viessmann · Vitocal 100-AW AM2V
The Service menu gives access to the actuator test function for the indoor unit.
- Open the Service menu.
- When prompted, turn the navigation dial to code 45 and press to confirm.
- Use the actuator test as needed.
- Choose End to return to the Service menu.
Outdoor unit point check function (press count readout)
Viessmann · DLCLRC outdoor unit
The outdoor unit display can step through 19 data points by repeated presses of the check function. Press 00 is normal display. The full readout list is in the setting table on the next item.
- Use the outdoor unit check function. Press it the number of times shown in the readout table to select the data.
- Press 00 (normal display) to return to running frequency, running state or malfunction code.
Outdoor unit point check function (SW1)
Viessmann · DLCURA outdoor unit PCB
Push SW1 on the outdoor PCB while the unit runs. The display cycles through live data for each press. Press 00 returns to normal display.
- Press SW1 on the outdoor PCB to step through the displayed values.
- Read the value for the needed point (see the point check table).
- Press 00 to return to normal display of running frequency, running state or fault code.
Point check (information enquiry)
Viessmann · DLFSOAH09XAK, DLFSOAH18XAK
Step through the unit's live readings from the remote or display. Each item name shows for about 2 seconds, then the value shows for about 25 seconds.
- Press LED DISPLAY or AIR DIRECTION to move to the next or previous item.
- Read the item name, then the value as listed in the point check table.
Reactor resistance check and S-line measuring points
Viessmann · Vitocal IND-A DLFUAA air handler, models 18XAK to 60XAK
Use a multimeter to check the reactor with the capacitor disconnected. A good reactor reads around zero ohms; otherwise it has failed. For the S-line DC voltage test, the red probe goes to 2 (L2 or S) and the black probe goes to 3 (N or S). Normal running shows alternating positive and negative values. A constant positive value means an outdoor fault; no change means an indoor fault.
- Disconnect the reactor from the capacitor and measure its resistance.
- Replace the reactor if the reading is not close to zero ohms.
- For the S-line test, connect the red probe to 2 (L2/S) and the black probe to 3 (N/S).
Read the Screen 1 live data columns
Viessmann · Vitocal 100-WA
Screen 1 updates once per second. The column order is fixed, so read the sensor and output values in that order when checking the unit.
- Check column 2 for the operating state (H, H RL, H RM, H MP).
- Check SH and EEV for superheat and expansion valve position.
- Check HP and LP (psi) for high and low side pressure.
- Check CL, CH, FC, HW, AR, AS, LI and LO for compressor, freeze, tank, air and loop temperatures.
- Check column 17 (LFL) for gas percentage or a sensor error code.
- Check C, F and W for compressor, fan and water speed in percent of full speed.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.