Viessmann Heat Pump: Limit buried refrigerant pipe length
Limit buried refrigerant pipe length on a Viessmann heat pump: Do not bury more than 36 in. (914 mm) of refrigerant pipe. Any buried section needs a 6 in. (152 mm) vertical rise to the outdoor unit valve connections. Over-length buried pipe can let refrigerant migrate during shutdown and cause liquid slugging that may damage the compressor at start-up.
Applies to: Refrigerant piping runs
How to fix limit buried refrigerant pipe length: step by step
- Keep buried refrigerant pipe to 36 in. (914 mm) maximum.
- Provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections on any buried section.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
More commissioning tips for heat pump
Source: Viessmann DLCURA installation instructions, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.