Viessmann Heat Pump: Evaporator low temperature protection (T2)
Evaporator low temperature protection (T2) on a Viessmann heat pump: Compressor frequency is limited when the indoor coil temperature gets low, which can happen in cooling or drying.
Applies to: DLCLRC indoor coil
Common causes of evaporator low temperature protection (t2)
- Indoor coil temperature T2 too low
How to fix evaporator low temperature protection (t2): step by step
- If T2 is below 32°F (0°C), the compressor stops and restarts when T2 reaches 41°F (5°C).
- If T2 is between 32°F and 39.2°F (0°C to 4°C), the frequency drops to a lower level.
- If T2 is between 39.2°F and 44.6°F (4°C to 7°C), the compressor holds the current frequency.
- If T2 is above 44.6°F (7°C), the frequency is not limited.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Vitocal 100-S DLCLRC service instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.