Viessmann Heat Pump: Compressor discharge temperature protection (T5)
Compressor discharge temperature protection (T5) on a Viessmann heat pump: Running frequency is limited when the compressor discharge temperature rises.
Applies to: DLCLRC compressor
Common causes of compressor discharge temperature protection (t5)
- Discharge temperature rises above the protection limits
How to fix compressor discharge temperature protection (t5): step by step
- If T5 is above 239°F (115°C) for 5 seconds, the compressor stops and restarts only after T5 falls below 194°F (90°C).
- If T5 is between 221°F and 239°F (105°C to 115°C), the frequency drops to a lower level every 2 minutes.
- If T5 is between 221°F and 230°F (105°C to 110°C), the frequency holds at the current level.
- If T5 is below 221°F (105°C), there is no frequency limit.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Vitocal 100-S DLCLRC service instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.