Viessmann Heat Pump: Communication signal voltage interpretation (S line, port 2 to port 3)
Communication signal voltage interpretation (S line, port 2 to port 3) on a Viessmann heat pump: Interprets the DC voltage on the communication line between the outdoor unit ports 2 and 3, or S and N, or L2 and S.
Applies to: DLCLRC outdoor unit
How to fix communication signal voltage interpretation (s line, port 2 to port 3): step by step
- Measure with the red probe on port 2 (or S or L2) and the black probe on port 3 (or N or S).
- Normal running: voltage alternates between positive and negative values.
- Outdoor unit fault: voltage is always positive.
- Indoor unit fault: voltage stays at one fixed value.
- To check a reactor, measure its resistance with no capacitor connected. A normal reactor reads close to zero ohms. Otherwise the reactor is faulty.
- Readings in the reference images are for guidance only. Actual values can vary.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCLRC Service Manual, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.