Updated · by Aurora Star Tech Inc.

4-way reversing valve check on a Viessmann heat pump: Checks the reversing valve voltage in cooling mode and the coil resistance with the power off.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DLCSRB outdoor units

How to fix 4-way reversing valve check: step by step

  1. Power on the unit and use a digital tester to measure the voltage while the unit runs in COOLING mode.
  2. Confirm the voltage reads 0 V. If it does not, replace the PCB.
  3. Turn off the power.
  4. Measure the coil resistance with a digital tester.
  5. Expected reading is 1.8 to 2.5 k (printed as KW on the page). Replace the valve coil if it is out of range.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Source: DLCSRB Service Manual, p. 51. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977