Viessmann Boiler: Wiring a floating call for heat contact
Wiring a floating call for heat contact on a Viessmann boiler: A dry contact on terminals 5 and 6 of plug lH sets the boiler demand.
Applies to: Vitodens 100-W B1HE/B1KE
How to fix wiring a floating call for heat contact: step by step
- Connect the dry contact to plug lH, terminals 5 and 6.
- Contact closed: demand for the set target value; boiler and heating circuit pump switch on.
- Contact open: no demand, no heating operation.
- Assign the function in the commissioning assistant under Commissioning.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W B1HE/B1KE installation manual, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.