Viessmann Boiler: Verify or change fuel type (natural gas or LPG) in service mode
Verify or change fuel type (natural gas or LPG) in service mode on a Viessmann boiler: Use the selector dials to enter the fuel setting while SERV is shown.
Applies to: Gas type change
How to fix verify or change fuel type (natural gas or lpg) in service mode: step by step
- Turn both selector dials to the centre position at the same time. SERV shows.
- Within 2 seconds turn selector dial tr counter-clockwise to O. A and the setpoint flash.
- Turn the other selector dial to set 0 for natural gas or 1 for LPG.
- Wait 15 seconds without touching the dials to save the setting.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Viessmann Vitodens 100-W WB1B installation and service instructions, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.