Service & test modes: Boiler tips (part 8 of 10)
Short, practical technician tips on service & test modes for boiler. Check each one against the manual for your exact model before acting.
Search for other stored faults
Viessmann · Vitotronic 300 GW2
Other fault codes stored in the control can be called up from the fault display.
- Press the search button once.
- Use the up or down button to scroll through other stored fault codes.
Service and diagnostic functions overview
Viessmann · Vitotronic 200 KW2 control unit
Functions reached through button combinations on the control. Exact button symbols are not legible in this extract.
- Temperatures, boiler coding cards and scans: use the listed button combination and press to enter.
- Relay test: use the listed button combination and press to enter.
- Error history: use the listed button combination and press to enter.
- Operating status: press the operating status button immediately to view.
- Service scan: press when Service is flashing on the display.
- Fault search: press when Fault is flashing on the display.
- Display contrast: press the combination to darken, or the other combination to brighten the display.
Service due reminder limits
Viessmann · Vitocrossal 300 CA3B
The service reminder is driven by coding 21 and 23 in the Boiler group. When either limit is reached, Service and the service symbol appear on the display.
- Set the hours-run limit in coding 21 in the Boiler group.
- Set the time interval limit in coding 23 in the Boiler group.
- When a limit is reached, the Service message and symbol will show.
Service level overview
Viessmann · Vitotronic 300 GW2
Button combinations to reach the service functions.
- Temperatures, boiler coding cards and scans: menu and reset buttons together for about 2 seconds, exit with OK (p. 73).
- Relay test: menu and OK together for about 2 seconds, exit with OK (p. 68).
- LON participant check: w and OK together for about 2 seconds, exit by pressing w and OK for about 1 second (p. 66).
- Operating status information: press the status button (p. 77).
- Service scan (when Service is flashing): press OK (p. 74).
Service level summary (Vitotronic 300-K)
Viessmann · Vitotronic 300-K, MW1S
Quick list of service functions on the Vitotronic 300-K and how to enter and exit each one. Button symbols on the source page are partly garbled, so check the button layout on the unit or the manual before use.
- Adjust display contrast: press OK and + together to darken, or OK and - together to lighten.
- Participant check: hold the flagged buttons together for about 2 seconds; exit by pressing them for about 1 second (page 76).
- Relay test: hold the flagged buttons for about 2 seconds, then press OK; exit with OK (page 81).
- Boiler sequence: hold the flagged buttons for about 2 seconds, then press OK; exit with OK (page 81).
- Temperatures and scans: hold the flagged buttons for about 2 seconds, then press OK (page 91).
- Operating status: press the flagged button to enter and exit (page 93).
- Maintenance requirement indication: press OK when maintenance flashes (page 94).
- Troubleshooting: press the flagged button to enter, then OK (page 99).
- Error history: hold the flagged buttons for about 2 seconds, then press OK (page 105).
- Reset codings to factory settings: hold the flagged buttons for about 2 seconds, press the flagged button, then confirm with OK (page 147).
- Coding 1: hold the flagged buttons for about 2 seconds; exit after about 1 second (page 148).
- Coding 2: hold the flagged buttons for about 2 seconds, confirm with OK; exit after about 1 second (page 151).
Service menu overview
Viessmann · Vitodens 200-W B2HA 45, 60
Service level menus: Diagnosis, Actuator test, Coding level 1, Brief scan, Coding level 2, Fault history, Service functions, Terminate service, plus General, Heating circuit 1/2/3, DHW, Solar, Reset data, Participant check, Service PIN, Service reset, Filling, Venting, Maximum output, Enter Vitocom PIN code and Multi-boiler system.
Service messages on Vitotronic 100
Viessmann · Vitotronic 100 GC1B
A flashing service symbol means the system is due for service. Service can be triggered by time (e.g. 12 months), flue gas temperature (e.g. 302° F / 150° C, GC1B only) or burner hours (e.g. 2500 hr). Vitotronic 300-K has no service interval, so it shows no service message.
- Notify your heating contractor of the service message.
- Acknowledge the message by pressing OK.
- If the service is postponed, the message comes back after 7 days.
- To view an acknowledged service message again, press and hold OK for about 4 seconds.
Service operation display (j)
Viessmann · Lago FB remote control
In service operation the boiler set point is coded 8, the pump runs, and the mode turns off after 15 minutes.
Setting lower and upper heating output for combustion testing
Viessmann · Vitodens 100-W
Forces the burner to run at minimum or maximum heating output through the burner modulation menu.
- Open the service menu with the button combination on page 60.
- Select Burner mod. set value and press OK.
- Select Minimum heating output and press OK. The burner runs at low output.
- Select Maximum heating output and press OK. The burner runs at high output.
- Ensure adequate heat transfer while testing.
Simulate a room thermostat call on the R-Stat input
Viessmann · Versatronik 10.WB1 space heating call
The manual says a room thermostat call is made by shorting the R-Stat terminals X3.1 and X3.2. This is the normal-mode way to start the space heating pump and boiler call for testing.
- Short terminals X3.1 and X3.2 (R-Stat) to simulate a room thermostat call.
- Confirm the space heating pump output turns on.
- Remove the short to end the call.
Start emissions test mode
Viessmann · Vitodens 100-W B1HE/B1KE
For certified contractors only. Test mode is started from the service menu and is best done during the heating season.
- Call up the home screen and open the menu.
- Select Settings, then tap OK.
- Select Service, then tap OK.
- Select Test mode, then select Yes and tap OK.
- Select Test mode again and tap OK.
- Select Start and tap OK.
Start filling or venting function
Viessmann · Vitodens 200-W B2HA 45, 60
Enter the service functions to start the Filling or Venting function. The second button symbol is not shown in the text.
- Press OK and the second button shown in the manual at the same time for about 4 seconds.
- Select Service functions.
- Select Filling (for fill) or Venting (for air purge).
- End the function by pressing OK or the arrow button.
Start the relay test
Viessmann · Vitotronic 100 GC1 and Vitotronic 300-K MW1S
Enter the relay test to switch each output on or off for checking wiring and actuators. The button symbol for the first key is missing in this text; check the manual's button graphic before use.
- Press the 9 button and the second button shown in the manual together for about two seconds.
- Select the relay output with the up or down arrow.
- Press OK to activate the output.
- Press OK again or exit the test to return to normal operation.
Start the venting program
Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352
Service menu access for the venting program used to purge the boiler and system.
- Press OK and the second button shown together for about 4 seconds.
- Select 'Service functions'.
- Select 'Venting'.
- Confirm that the venting function is enabled.
- Press OK or the back button to end the venting function.
Temperatures and brief scans (Vitotronic 300-K)
Viessmann · Vitotronic 300-K, MW1S
Shows live temperatures, outputs and states. Items shown depend on what is connected, such as sensors, DHW tank sensors, supply temperature sensor and remote control.
- Hold the flagged buttons together for about 2 seconds.
- Select the required scan with the up or down button.
- Press OK to view it.
- Read the outdoor temperature (actual and dampened), boiler sequence, boiler output percentage and integral, boiler temperatures 1 to 4, sensor 17A and 17B values, DHW and supply temperatures, and room temperature.
- To reset the dampened outdoor temperature to the actual value, use the reset button shown on the scan screen.
- Negative integral values mean start-up integral, positive values mean shutdown integral.
Test and manually adjust the mixing valve motor
Viessmann · Mixing valve motor 7133 390
Use the control unit relay test to run the mixing valve open and closed. For manual adjustment, disengage the motor drive before moving the valve by hand.
- Run the relay test on the control unit so the mixing valve moves open and closed.
- To adjust by hand, lift the motorized lever up.
- Unhook the mixing valve handle.
- Remove plug A from the motor.
- For 24V actuators, follow the instructions supplied with the actuator.
Test relay outputs (actuator test)
Viessmann · Vitodens 222-F B2TB
Use the actuator test to switch individual outputs on and check them.
- Enter the service level.
- Select 'Actuator test'.
- Select the output to test and check that it switches as listed in the actuator test table.
Test the fixed high limit (FHL)
Viessmann · Fixed high limit
Functional check of the fixed high limit. Boiler and burner must be watched the whole time.
- Deactivate low-temperature floor heating, with or without mixing valves, before starting.
- Isolate attached DHW tanks and confirm the expansion tank will take the water expansion.
- Let boiler water cool to 140 °F / 60 °C before activating any heat distribution system.
- Press and hold the FHL test switch. Never tape or otherwise hold it in place.
- The adjustable high limit is bypassed, so the burner runs until the fixed high limit trips.
- When the burner shuts off, release the test switch.
- Wait until boiler water is 27 °F / 15 °C below the selected safety temperature, then press the reset button.
Test the fixed high limit with the test button
Viessmann · Fixed high limit
The test button on the fixed high limit checks that it works. The full test description is on page 72 of the manual.
- Press the test button on the fixed high limit.
- Check that the limit shuts the boiler down with lockout.
- Reset the limit manually after the test.
Test the high limit safety cut-out
Viessmann · Vitodens 100-W B1HE/B1KE
Checks the high limit safety cut-out from the service menu. Settings and functions in the service section are covered in the installation and service instructions.
- Call up the home screen and open the menu.
- Select Settings, then tap OK.
- Select Service, then tap OK.
- Select Yes, then tap OK.
- Select Test high limit safety cutout, then tap OK.
- Select Yes and tap OK.
Testing the mixing valve motor with the relay test
Viessmann · Mixing valve circuit extension kit
The control unit relay test drives the mixing valve open and closed.
- Start the relay test on the control unit.
- Confirm the mixing valve moves to open and then to close.
Update LON participants
Viessmann · Vitotronic 200-H LON fault manager
Only possible when all users are connected and the control unit is programmed as fault manager (code 79:1). The participant list is updated after about 2 minutes.
- Press the w key and the second key together for about 2 seconds to start the participant check.
- Press D to update the participant list.
- Wait about 2 minutes for the update to complete.
Update the LON participant list
Viessmann · Vitotronic 300-K, MW1S
The participant list can only be updated when all participants are connected and this control is the fault manager (coding 79 : 1, factory default). Only one Vitotronic in a system can be the fault manager. Button symbols are not clearly printed here.
- Press the two buttons shown on the page together for about 2 seconds to start the participant check.
- Press the button shown on the page.
- Wait about 2 minutes. The participant list is updated and the check is complete.
Using the help text
Viessmann · Vitotronic 200 KW6B programming unit
The programming unit has context-sensitive help that explains the selected menu.
- If the screen saver is active, press ? to open the short guide.
- From anywhere in the menu, hold the key until the standard menu appears, then press ?.
Venting program
Viessmann · Heating system venting
The venting program runs the circulation pump on and off in alternating 30-second periods over 20 minutes. The burner stays off during this program.
- Activate the venting program as described in Venting the heating system (not on these pages).
Verify or change fuel type (natural gas or LPG) in service mode
Viessmann · Gas type change
Use the selector dials to enter the fuel setting while SERV is shown.
- Turn both selector dials to the centre position at the same time. SERV shows.
- Within 2 seconds turn selector dial tr counter-clockwise to O. A and the setpoint flash.
- Turn the other selector dial to set 0 for natural gas or 1 for LPG.
- Wait 15 seconds without touching the dials to save the setting.
View all DHW time cycles on the time line
Viessmann · DHW time program
Shows the preset DHW time cycles as a graphic time line without changing them.
- Open the programming unit cover.
- Press the heating circuit selector until it lights up.
- Press the two buttons shown in the manual at the same time to display the time line.
- Close the cover.
View and delete the fault memory (error history)
Viessmann · Vitotronic 100 GC1 with DBGU programming unit
The control keeps the last 10 fault codes, numbered from the most recent. Use this to check for repeat faults.
- Press the two keys shown together for about 2 seconds to enter the error history.
- Scroll through the saved fault codes with the arrow keys; fault 1 is the most recent.
- To clear all saved codes, use the delete key.
- Press the exit key to leave the history.
View error history
Viessmann · Vitotronic 200 KW2
Opens the stored error history. The manual does not show the full procedure on these pages.
- Press the two buttons together as shown in the manual to open the error history.
View fault memory
Viessmann · CA3B Series 2.5 to 6.0
The last 10 faults are stored and can be read. The display times out after 20 seconds with no key press. The fault memory can show a cause even when no code is displayed for a non-lockout fault.
- Hold the S button for more than 2 seconds until the indicator flashes.
- Turn the dial until 4 shows under Service.
- Press S. A 4 shows under Status.
- Use Y or B to choose 1 Display fault codes, 2 Detail fault codes or 3 Clear fault memory.
- Press S to open the selected view.
- Use Y or B to scroll through the fault codes.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.