Verify gas input by clocking the meter on a Viessmann boiler: Verify burner input by timing the gas meter with all other gas appliances off. Input is correct when it matches the nameplate input. A boiler underfired by up to 5% is acceptable. Never overfire.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA

How to fix verify gas input by clocking the meter: step by step

  1. Get the correct heating value of the gas from the gas utility before timing.
  2. Turn off all other gas appliances served by the meter.
  3. Time how long the boiler takes to use 10 ft3 of gas, in seconds.
  4. Calculate Btu/h as 3600 x 10 divided by the seconds, multiplied by the heating value.
  5. Example: 68 s with 1000 Btu/ft3 gives 530000 Btu/h for the 530 model.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More commissioning tips for boiler

Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 30. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.