Commissioning: Boiler tips (part 18 of 21)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.

Use variable speed pump for zone flow

Viessmann · Application 2 pump selection

A variable speed circulator for P3 adjusts flow as zone valves open and close. A single speed pump needs a pressure differential bypass to avoid over-pumping a single circuit.

  1. Select a variable speed circulator for P3 when possible.
  2. If a single speed pump is used, install a pressure differential bypass in the system.

Venting and common vent limits

Viessmann · Flue and combustion air venting

Only common vent with other Vitodens 200-W boilers of the same size. Side wall coaxial vent installs must include the Viessmann protective screen. Do not exceed the maximum equivalent length in the Venting System instructions. The coaxial vent transition adds about 65 mm (about 2.5 in.) to the overall dimension.

  1. Confirm the other boilers on the common vent are Vitodens 200-W of the same size.
  2. Fit the Viessmann protective screen on side wall coaxial vents.
  3. Check the equivalent vent length against the Venting System instructions.

Venting codes and chimney requirements

Viessmann · Vitorond 100 VR1 boilers

Install the vent system to all applicable local and national codes, and make sure any side wall vent meets the manufacturer's requirements.

  1. Follow local codes; in Canada use CSA B139-00, in the U.S. use NFPA 31.
  2. Build masonry or concrete chimneys to the provincial or state building code, or to CSA A405 (Canada) or NFPA 211 (U.S.). Metal chimneys must also meet Chapter 4 of NFPA 211.
  3. In Canada, use factory built chimneys that conform to CAN/ULC-S629 (1202°F / 650°C), CAN/ULC-S604 Type A, or CAN/ULC-S609 Type L.
  4. In Canada, install factory built chimneys per the manufacturer's certified instructions.
  5. In Canada, provide a clean-out with a tight-fitting removable cap so no air can enter when it is in place.
  6. In the U.S., factory built chimneys must meet NFPA requirements and be listed, installed and used per their listings and manufacturer instructions.

Venting route and piping support

Viessmann · Vitodens 200-W B2HA 45, 60

The vent can be single-wall or coaxial. Route it through the side wall or roof by the shortest practical path, rising at least 3 degrees. The piping must be supported on its own and must not rest on or hang from the boiler.

  1. Run the venting system by the shortest route, rising at a minimum of 3 degrees.
  2. Support all piping with a proper hanger method so no load goes onto the boiler.
  3. Use only a moderate amount of pipe dope.
  4. If using single-wall venting that relies on room air, remove the outer gasket on the vent adaptor.

Verify a carbon monoxide alarm is installed

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

Before start-up, confirm at least one CO alarm is installed in the living space, following the alarm maker's instructions and local codes.

  1. Check that a CO alarm is installed in the residential living space.
  2. Install it per the alarm manufacturer's instructions and local codes if missing.

Verify CO alarm before start-up

Viessmann · Vitotronic 100 KW10B

Installer must confirm at least one carbon monoxide alarm is installed in the living space, per the alarm maker's instructions and local codes, before the appliance is put into operation.

  1. Confirm a CO alarm is installed in the residence per the alarm maker's instructions and local code.
  2. Only then start the appliance.

Verify combustion after startup

Viessmann · Oil-fired VR1 boilers with factory-mounted burners

Check combustion results of the oil burner after startup. If adjustment is needed, confirm the results with a calibrated flue gas analyzer.

  1. Start the burner and check combustion with a calibrated flue gas analyzer.
  2. Adjust the burner only if results are out of range, then recheck.

Verify DHW sensor and add a tempering valve with a non-Viessmann tank

Viessmann · Vitodens 200-W B2HB DHW storage installations

If the DHW tank is not a Viessmann Vitocell 100 or 300, the sensor operation must be verified with the tank maker. A temperature tempering valve is strongly recommended in the DHW supply.

  1. Confirm the DHW tank sensor works correctly with the tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

Verify DHW tank sensor with non-Viessmann tanks

Viessmann · Multi-boiler and single-boiler DHW tank layouts

If a DHW storage tank other than a Viessmann Vitocell 100 or 300 is used, the installer must confirm the Viessmann DHW tank temperature sensor works correctly with the tank manufacturer. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. Check with the original tank manufacturer that the Viessmann DHW sensor works with the tank.
  2. Install a temperature tempering valve in the DHW supply line.

Verify field-supplied controls

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

The heating contractor must confirm that all field-supplied controls and components work correctly before handover.

  1. Check low water cut-offs, flow switches (if used), staging controls, pumps, motorized valves, air vents and thermostats.

Verify field-supplied controls before start-up

Viessmann · Vitorond 100 VR1 boilers

The heating contractor must confirm that field-supplied controls and components work correctly. Thermostats, pumps, zone valves and other controls are not supplied by Viessmann.

  1. Check low water cut-offs (if used).
  2. Check flow switches (if used), staging controls, pumps, motorized valves, air vents and thermostats.
  3. Confirm all of these work before leaving the boiler running.

Verify field-supplied safety controls

Viessmann · Vitotronic 100 KW10B

The contractor must check that field-supplied controls are complete and working. These include low water cut-offs, flow switches if used, staging controls, pumps, motorized valves, air vents and thermostats.

  1. Check low water cut-offs.
  2. Check flow switches if used.
  3. Check staging controls, pumps, motorized valves, air vents and thermostats.

Verify gas input by clocking the meter

Viessmann · Vitodens 200-W B2HA

Verify burner input by timing the gas meter with all other gas appliances off. Input is correct when it matches the nameplate input. A boiler underfired by up to 5% is acceptable. Never overfire.

  1. Get the correct heating value of the gas from the gas utility before timing.
  2. Turn off all other gas appliances served by the meter.
  3. Time how long the boiler takes to use 10 ft3 of gas, in seconds.
  4. Calculate Btu/h as 3600 x 10 divided by the seconds, multiplied by the heating value.
  5. Example: 68 s with 1000 Btu/ft3 gives 530000 Btu/h for the 530 model.

Verify mixing valve stroke direction

Viessmann · Application 9 mixing valves

The stroke direction of the mixing valve motors must be checked with an actuator test.

  1. Run an actuator test on each mixing valve motor.
  2. Confirm the valve strokes in the correct direction.
  3. Refer to the Installation and Service Manual of the Cascade Control for the test procedure.

Verify the system diagrams on site

Viessmann · System versions 7 to 10

The connection diagrams are only recommendations. Check them for completeness and function at the installation site. Single-phase and three-phase pumps must be wired through field-supplied motor contactors or motor starters.

  1. Verify the wiring against the site, and confirm completeness and function.
  2. Use field-supplied motor contactors or motor starters for single-phase and three-phase pumps.

Water connections and minimum system pressure

Viessmann · Vitodens 222-F, B2TB 68 and 125

Boiler can be used in any fully pumped hot water heating system. Minimum system pressure is 14 psig.

Water quality for fill water

Viessmann · Heating system fill water

Use potable water and flush the system first. Soften water harder than 8.77 grains or 150 ppm TDS. Heating inhibitors or antifreeze may be added by hand.

  1. Flush the entire heating system before filling.
  2. Use only potable quality water.
  3. Soften water above 8.77 grains / 150 ppm TDS.
  4. Add suitable inhibitor or antifreeze manually if needed.

Water quality for filling the heating system

Viessmann · Vitocrossal 300 CU3A 26 to 199

Unsuitable fill water causes deposits and corrosion that can damage the equipment.

  1. Flush the entire heating system before filling.
  2. Use only water of potable quality.
  3. Soften the water if it is harder than 8.77 grains / 150 ppm total dissolved solids.
  4. Add inhibitors or antifreeze suitable for heating systems manually if needed.

Water quality, antifreeze and corrosion protection

Viessmann · Vitodens 222-F, B2TB 68 and 125

Corrosion is not typical in correctly installed and operated sealed systems. Use only corrosion inhibitors approved for boilers with single-wall DHW heat exchangers when required by plastic pipe makers. Treat fill water in areas of high mineral content or hardness. If antifreeze is used, maximum content is 50% for this boiler, use only hot water heating antifreeze, and never automotive silicate antifreeze. Check the system often when filled with antifreeze. Tell the owner the system contains glycol and provide the antifreeze MSDS. Antifreeze may require a backflow preventer and can affect expansion tanks and other components.

  1. Verify inhibitor or antifreeze is approved for hot water heating boilers.
  2. Keep antifreeze at or below 50%.
  3. Check glycol concentration regularly.
  4. Give the owner the MSDS and tell them the system is glycol-filled.

Water treatment and freeze protection

Viessmann · Vitotron 100 VLN2 hydronic system

Treated water extends heating element life and reduces sediment. Only certain glycol may be used.

  1. Fill the boiler and system with soft or distilled water where possible.
  2. Use only propylene glycol freeze protection that is non-toxic and corrosion resistant.
  3. Keep propylene glycol at no more than 50% by volume.
  4. Never add methanol or ethylene glycol (automotive antifreeze).

Waterside design: low-loss header preferred

Viessmann · Vitodens 200-W B2HB 19 to 199

Viessmann prefers a low-loss header over closely spaced tees. The boiler's built-in low-loss header logic works with the header through sensor communication. Primary/secondary piping with closely spaced tees is an alternative if needed.

  1. Size the low-loss header from the system flow tables on pages 11 to 13.
  2. Connect the low-loss header sensor as required by the header sizing table.
  3. Confirm the boiler flow stays within the maximum flow rate for the model.

Waterside flow and low-loss header

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The boiler is for closed loop, forced circulation hot water systems only. Size pipe using the standard friction loss method and stay within the boiler minimum and maximum flow rates. Max flow is 14.3 GPM (3,250 L/h). If system flow exceeds the max, falls below the min, or is unknown, a low-loss header is strongly recommended. Primary-secondary piping with closely spaced tees is an alternative, but a low-loss header is preferred. The built-in low-loss header logic in the boiler maintains the required temperature rise through communication with the header. The temperature rise text in the manual is partly garbled.

  1. Size the piping using the standard friction loss method.
  2. Confirm the system flow is within the boiler limits (min to 14.3 GPM).
  3. If flow is above max, below min, or unknown, install a low-loss header.
  4. Refer to the Technical Data manual for low-loss header information.
  5. Check pressure drop from the primary circuit chart when sizing the circulator.

Weishaupt boiler/burner start-up must be done by Viessmann

Viessmann · Vitorond 200 VD2 boilers with Weishaupt burners

Vitorond 200 VD2 boilers with Weishaupt burners must be started up by Viessmann. Ask Viessmann for the start-up prerequisites.

  1. Contact Viessmann to arrange the boiler/burner start-up.
  2. Ask for the start-up prerequisites before the visit.

When to use a low-loss header

Viessmann · Vitodens 100-W WB1B 26 and 35 in all system layouts

A low-loss header is recommended when the water flow is below 1.7 GPM (400 L/h) or above 6.2 GPM (1400 L/h). It is strongly preferred over closely spaced tees.

  1. Check the system flow rate against the 1.7 GPM and 6.2 GPM limits.
  2. If flow is out of range, fit a low-loss header, using the accessory size that matches the flow.

WiFi router and network requirements

Viessmann · Vitodens 100-W B1HE/B1KE

The router and network must meet these requirements before commissioning.

  1. Protect the WiFi router with a WPA2 password.
  2. Keep the router firmware updated.
  3. Do not use unencrypted connections between the boiler and the router.
  4. Use a flat rate internet connection with no time or data limit.
  5. Use dynamic IP addressing (DHCP, factory setting); have an IT expert check or set this up.
  6. Enable ports 80, 123, 443 and 8883 for direct outward connections; have an IT expert check or set this up.

Wire size and wire type for field wiring

Viessmann · All field wiring on the boiler

Supply wiring to the boiler and other control wiring must be 14 ga. or heavier. If the factory wire must be replaced, use 105°C wire or equivalent.

Wiring a mixing valve controller

Viessmann · Vitodens 222-F, B2TB 68 and 125

Multiple 145 communication accessories are connected by daisy chain, running cable device to device. Set the S1 switch to assign the mixing valve to the heating circuit. Wiring terminals are shown on page 18 of the manual.

  1. Daisy-chain multiple 145 communication accessories device to device.
  2. Set switch S1 to assign the mixing valve heating circuit.

Zero-clearance venting and service clearances

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The boiler is listed for zero clearance to combustibles with approved venting. Leave 12 in. (305 mm) at the side where practical for rating plate access and the PRV kit.

  1. Vent with single-wall special venting (AL-29-4C) or UL/ULC-listed CPVC/PPs gas vent material to use zero clearance to combustibles.
  2. Leave 12 in. (305 mm) side clearance where practical to view the rating plate and fit the PRV kit.
  3. If the PRV is turned 90° facing forward using an extension, the side clearance can be reduced; the reduced figure is not legible in this copy, so check the manual's clearance table.
  4. Closet and alcove installation is approved with the clearances listed in Table 1; confirm them against the full table before installing.
  5. See the Vitodens 200-W B2HB Venting System Installation Instructions for venting details.

Zone circuit pump connections

Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125

Up to 2 zone circuit pumps can connect directly to the boiler. Extra pumps need the AM1 extension module (accessory). Pump outputs are assigned in the start-up wizard.

  1. Connect up to 2 zone circuit pumps to the boiler.
  2. For more pumps, install the AM1 extension module and connect the pumps there per its installation instructions.
  3. Assign pump outputs in the start-up wizard.
  4. See the boiler service instructions for start-up.

Zone circuit pump limits and assignment

Viessmann · Models 45, 57, 160, 199

Pump outputs are assigned during the start-up wizard. Only two zone circuit pumps connect directly to the boiler; more require an AM1 extension module.

  1. Assign the pump outputs using the start-up wizard.
  2. Connect no more than 2 zone circuit pumps directly to the boiler.
  3. For additional pumps, use an AM1 extension module and follow its installation instructions.
  4. Refer to the boiler service instructions for start-up.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.