Viessmann Boiler: Venting through an insulated chase or masonry flue
Venting through an insulated chase or masonry flue on a Viessmann boiler: Vent material may extend beyond the outside wall only inside an enclosed, insulated, waterproof chase for outdoor use. Space around a chimney liner or existing masonry flue must not be used as combustion air supply. A separate air intake can run in that space if the vent is approved for zero clearance.
Applies to: Vitocrossal 200 CI2 vent routing
How to fix venting through an insulated chase or masonry flue: step by step
- Build an enclosed, insulated, waterproof chase if vent runs outdoors beyond the wall.
- Do not draw combustion air from the space around a chimney liner or masonry flue.
- Use a separate combustion air intake pipe run beside the vent only if the vent is approved for zero clearance.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Installation Instructions, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.