Viessmann Boiler: Test and manually adjust the mixing valve motor
Test and manually adjust the mixing valve motor on a Viessmann boiler: Use the control unit relay test to run the mixing valve open and closed. For manual adjustment, disengage the motor drive before moving the valve by hand.
Applies to: Mixing valve motor 7133 390
How to fix test and manually adjust the mixing valve motor: step by step
- Run the relay test on the control unit so the mixing valve moves open and closed.
- To adjust by hand, lift the motorized lever up.
- Unhook the mixing valve handle.
- Remove plug A from the motor.
- For 24V actuators, follow the instructions supplied with the actuator.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Viessmann Vitotronic 300-K MW1S installation and service instructions, p. 128. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.