Viessmann Boiler: Δt control for condensing
Δt control for condensing on a Viessmann boiler: Δt control keeps a fixed spread between supply and return. At low load the pump speed is reduced so return temperature stays low. The target spread is interpolated between two points: at 68°F (20°C) supply it uses parameter 2779.0 (factory 9°F / 5 K), and at 194°F (90°C) supply it uses parameter 2779.1 (factory 36°F / 20 K).
Applies to: Vitocrossal 200 CI2 boilers
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 81. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.