Updated · by Aurora Star Tech Inc.

Simplified leak test on coaxial flue (annular gap) on a Viessmann boiler: Recommended during start-up for sealed-combustion coaxial vent only. Measure CO2 in the combustion air in the annular gap of the air intake pipe. Venting is considered tight if CO2 is 0.2% or lower, or O2 is 20.6% or higher. If readings are worse, check the venting system thoroughly. Not applicable to single-wall venting.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Coaxial sealed-combustion venting

How to fix simplified leak test on coaxial flue (annular gap): step by step

  1. Measure CO2 (or O2) in the air intake annular gap using the test port on the vent adaptor.
  2. Accept if CO2 is 0.2% or lower, or O2 is 20.6% or higher.
  3. If not, inspect the full venting system.
  4. Re-seal the test port with its plug after the test, otherwise room air is drawn in.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More commissioning tips for boiler

Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 49. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.