Commissioning: Boiler tips (part 16 of 21)
Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.
Set DHW temperature range before adjusting
Viessmann · DHW temperature setpoint, coding 56
The DHW setpoint is 50 to 140 F / 10 to 60 C by default. Coding 56:1 extends it to 50 to 203 F / 10 to 95 C. Observe the maximum DHW temperature and adjust the high limit before raising the range.
- Check the maximum allowed domestic hot water temperature.
- Set coding 56:1 only if a higher range is needed.
- Adjust the adjustable high limit to match.
Set high altitude operation
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Altitude setting uses coding address 93 in coding level 2, General.
- Set coding address 11 to 9 to unlock coding 93.
- Set 93:0 for altitudes up to 5,000 ft (1,500 m).
- Set 93:6 for altitudes from 5,000 ft to 10,000 ft (1,500 m to 3,000 m).
- After setting 93, set coding address 11 to 0.
- Do not set or use 93:1 to 93:5.
- The high altitude program turns off automatically after 20 minutes.
Set high limit to match safety equipment
Viessmann · All external control setups
Settings for fixed high limit and other values depend on the safety equipment installed per applicable codes.
- Confirm installed safety equipment before setting the fixed and adjustable high limits.
- Use the table values for the boiler type.
Set the boiler sequence
Viessmann · Vitotronic 300-K, MW2C
The control offers several boiler sequences, depending on the coding and internal calculations. Changing the sequence helps the boilers run evenly. The legend shows the start order (A) and the permanently assigned boiler numbers (B). The example shows boilers started in the order 4, 3, 2, 1, 8.
- From the home screen, select 'Boiler sequence'.
- Select 'New boiler sequence' and choose the required sequence.
Set the display language
Viessmann · Versatronik COMO OT
The language prompt appears only the first time the cover is opened after power-up. It appears again if the unit is removed from its base.
- Open the flap; the display shows ENGLISH.
- Press E to change the mode, then use Plus/Minus to choose the language.
- Press Save to store it and move to USER SETTING.
Set the rotary dial on the 2-wire BUS communication module
Viessmann · Vitotronic 200-H with 2-wire BUS communication module
The control connects to the Viessmann 2-wire BUS through a plug-in communication module. Its rotary dial sets the system version and must be unique on the bus. Position 4 is the default when a mixing valve actuator kit is used on a wall-mounted boiler, so do not duplicate it when adding a second Vitotronic 200-H.
- Plug the 2-wire BUS communication module into the control unit (accessory, see parts list).
- Set the rotary dial on the module to a system version between 4 and C.
- Make sure no other control unit on the bus uses the same rotary dial position.
- On a wall-mounted boiler with one mixing valve actuator kit, the default position is 4; when adding another Vitotronic 200-H, pick a position other than 4.
- If a boiler control unit for wall-mounted boilers or a Dekamatik system is connected, adjust the differential temperature at that control unit.
Set the time and weekday
Viessmann · Versatronik COMO OT
Time and day are set in the Time-Day level. Time changes in steps of 15 minutes, starting from :00, :15, :30 or :45.
- Open the cover so USER shows, then press Plus twice to reach TIME-DAY.
- Press Prog to show TIME and E, then use Plus/Minus to set the time. Hold the key to scroll faster.
- Press Prog to show DAY and E, then use Plus/Minus to set the weekday.
- Press Prog to save and return to TIME-DAY.
- Close the cover.
Set time and date (300-K only)
Viessmann · Vitotronic 300-K
Time and date are factory set. After the system has been shut down for a long time, check and reset them.
- Open the extended menu.
- Select "Settings", then "Time/Date".
- Set the time and date.
Set up Vitotronic 200 for coding in cascade mode
Viessmann · Vitotronic 200 on a multi-boiler (cascade) system
Put the boiler in cascade mode before coding a Vitotronic 200. The button names are missing from the text, so use the boiler's control keys as shown on the display.
- Press the menu key and OK together for about 4 seconds.
- Scroll to 'service' and select it with OK.
- Scroll to 'service functions' and select it with OK.
- Scroll to 'multi-boiler system' and select it with OK.
- When finished, press the exit key to leave.
Set Vitodens WB2B coding 00 to 00
Viessmann · Vitodens 200 WB2B with Vitotronic 100 HC1
Coding 00 cannot be set to 0 directly. The Vitodens boiler pump keeps running unless this is done correctly.
- Temporarily change coding 01 to 2 (multi-boiler). Listen for the click.
- Change coding 01 back to 1.
- Set address 34 to 23.
- Confirm coding 00 now reads 00.
Setting the altitude parameter
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
The factory default is set for altitudes up to 5,000 ft (1,500 m). For other altitudes, change the altitude using coding address 93 in coding level 2 (General).
- Enter coding level 2 (General).
- Set coding address 93 to the site altitude.
Setting the DIP switch for a separate room temperature sensor
Viessmann · Vitotrol 200 and Vitotrol 300 remote controls
When a separate room temperature sensor is connected, the matching DIP switch on the remote control PCB must be turned on. The switch differs between the two remotes.
- On Vitotrol 200, set DIP switch S6.3 to ON.
- On Vitotrol 300, set DIP switch S3.3 to ON.
Setting values during start-up
Viessmann · Versatronik 200 start-up screens
Each start-up screen shows the current value. Change it with the rotary knob, then confirm. Values follow the system selection; the Standard setting applies to the function screens.
- Open the start-up screen for the item (for example Boiler 1 type or Tank type).
- Turn the rotary knob to select the value that matches the system.
- Press OK to save, or Back to leave without changing it.
- Work through the screens in order so no value is skipped.
Shunt pump sizing for return temperature raising
Viessmann · System type 2, single-boiler with shunt pump and return valve (modulating boiler)
The shunt pump must be sized so that the bypassed water is about 30% of the boiler's total flow rate.
- Size the shunt pump so bypassed flow is approx. 30% of total boiler flow.
- Confirm the sensor T2 switches the shunt pump on when return temperature falls below the minimum.
Side wall coaxial vent and common venting
Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125
Do not common-vent this boiler with another appliance. A side wall coaxial vent must use the Viessmann protective screen and must not exceed the maximum equivalent length.
- Check the equivalent vent length against the Venting System Installation Instructions.
- Confirm the Viessmann protective screen is fitted to the side wall coaxial vent.
Side wall coaxial vent installation requirements
Viessmann · B2HB 45, 57, 160, 199
Do not exceed the maximum equivalent vent length in the Vitodens 200-W B2HB Venting System Installation Instructions. A Viessmann protective screen must be fitted on side wall coaxial vent installations.
- Check the equivalent length against the venting Installation Instructions before finalizing the run.
- Fit the Viessmann protective screen on the side wall coaxial vent.
Side wall vent termination
Viessmann · Side wall venting
Side wall vents use a termination elbow with screen. Exhaust and air intake piping outside must be UV resistant PP(s) when PP(s) is used. Snow level and grade heights apply.
- Fit a protective screen on the termination.
- Keep the exhaust terminal at least 12 in (305 mm) above grade or the expected snow level.
- Keep the intake terminal at least 12 in (305 mm) above grade or expected snow level.
- Use UV resistant polypropylene for exposed exhaust and intake piping on PP(s) systems.
- Caulk gaps around the vent and seal any penetrations.
Simplified coaxial vent leak test
Viessmann · Vitodens 200-W B2HA, all sizes
Check the air intake coaxial gap for leaks during start-up by measuring the combustion air. The vent is acceptable if CO2 is 0.2% or lower, or O2 is 20.6% or higher. If the readings are worse, check the venting system thoroughly.
- Use the two measurement ports on the vent pipe adaptor (one for air intake, one for flue gas).
- Measure CO2 in the combustion air in the coaxial gap of the air intake pipe.
- If CO2 is above 0.2% or O2 is below 20.6%, check the whole venting system for leaks.
Simplified leak test on coaxial flue (annular gap)
Viessmann · Coaxial sealed-combustion venting
Recommended during start-up for sealed-combustion coaxial vent only. Measure CO2 in the combustion air in the annular gap of the air intake pipe. Venting is considered tight if CO2 is 0.2% or lower, or O2 is 20.6% or higher. If readings are worse, check the venting system thoroughly. Not applicable to single-wall venting.
- Measure CO2 (or O2) in the air intake annular gap using the test port on the vent adaptor.
- Accept if CO2 is 0.2% or lower, or O2 is 20.6% or higher.
- If not, inspect the full venting system.
- Re-seal the test port with its plug after the test, otherwise room air is drawn in.
Slab curing function profiles
Viessmann · Vitotronic 300-K MW1S slab curing function
The slab curing function has four supply-temperature profiles over 30 days, selected with coding F1 (values 1 to 4). Profile curves are graphs only; no numeric table is printed.
- Set coding F1 to the profile needed (1, 2, 3 or 4). Coding is covered on the previous page (167).
- Check the supply temperature against the profile curve for the day of curing.
- Use the back-of-manual conversion chart if the temperature is needed in °F.
Solar multifunction conflict
Viessmann · Versatronik 200 controller, solar MF functions
If an MF solar function (07, 08, 09, 23, 27, 28 or 29) is active, no other external solar controller may be connected to the system.
- Before enabling an MF solar function, confirm no external solar controller is connected.
- Set F15 to 5 where the storage 3 switch-over functions (08, 09) are used.
Spring-loaded flow check valves during system fill
Viessmann · Vitorond 200 VD2A hydronic installations
Flow check valves must be open to fill and purge the system and closed again once it is purged.
- Open the spring-loaded flow check valves before filling the heating system.
- After the system is full and purged of air, close the flow check valves to restore flow-check operation.
Stainless vent and vacuum relief damper
Viessmann · Stainless steel venting
Stainless vent must be UL/ULC listed for Category IV. Where a sealed vertical vent is used, a vacuum relief damper may be needed for the rare case of a sudden burner interruption at full firing, such as a power failure.
- Check the single-wall vent parts were ordered and supplied correctly before installation.
- Fit a starter stainless adaptor at the boiler vent connection if needed. It is supplied by others.
- Check whether a vacuum relief damper is required for sealed vertical venting and install it per its own instructions.
- Seal gaps between the vent or air intake pipe and the wall with approved sealant or caulk.
Standard equipment and wall mounting
Viessmann · Vitodens 100-W B1HE and B1KE
The boiler ships fully piped and pre-wired with a 30 psig relief valve, air vent, pressure gauge, two fill/drain valves, mounting bracket and hardware, and the outdoor sensor. B1KE adds a DHW relief valve and B1HE adds a DHW tank sensor. Mounting screws are supplied for wood studs (2x4), metal studs and brick or concrete walls.
- Select the mounting screws that suit the wall type.
- Mount the bracket and boiler using supplied hardware.
- Connect all pipes at the bottom of the boiler.
Start-up must be done by a licensed heating contractor
Viessmann · All Vitodens 200-W B2HB models
Initial start-up and any adjustment, service or maintenance must be done by a licensed professional heating contractor. Complete the Maintenance Record in the service instructions.
- Complete the Maintenance Record at initial start-up.
- Show the system operator the system operation, shutdown and emergency shutdown.
Start-up of Weishaupt burner boilers
Viessmann · Vitorond 200 VD2A boilers with Weishaupt burners
Vitorond 200 VD2A boilers with Weishaupt burners require start-up by Viessmann. Ask Viessmann for the start-up prerequisites.
- Arrange boiler and burner start-up through Viessmann.
- Ask Viessmann for the required start-up prerequisites before scheduling.
Start-up precautions
Viessmann · Vitorond 100 oil-fired boiler
Several conditions must be met before the burner is started.
- Keep the fresh air intake of the boiler room open.
- Confirm the chimney and all flue pipes are connected, sealed and unobstructed.
- Do not start the burner unless the combustion chamber door is secured.
- Do not attempt to start the burner with excess oil accumulated, when the unit is full of vapor, or when the chamber is very hot.
- Do not fire the boiler without water.
- Do not use gasoline, crankcase drainings or oil containing gasoline.
- Do not leave tools inside the combustion chamber.
Start-up programming sequence
Viessmann · System Examples 02, 03 and 04
Applies to the start-up of the cascade system examples shown on these pages.
- Finish all wiring checks and make sure every connection is made before powering the control on.
- Power the control on. The start-up screen appears on the display.
- Press the button next to OK to enter the start-up sequence.
- Enter the values with the rotary dial and function keys.
- Use the programming table for the chosen system example. The variables shown depend on the system selection.
Start-up sequence
Viessmann · Versatronik 200 System Control
Complete all wiring checks before applying power. The start-up screen appears when the control is powered on.
- Complete all necessary connections before powering the control ON.
- Once the initial wiring checks are complete, power the control ON.
- When the start-up screen appears, press the button next to OK to enter the start-up sequence.
- Enter the required values using the rotary dial and function keys.
- Use the start-up programming table for the required values.
Start-up sequence on the Versatronik 200 control
Viessmann · System examples 07, 08 and 09
The start-up screen is entered from the OK prompt. The values shown depend on the system selection, so use the table that matches the installed system example.
- Finish all initial wiring checks before powering the control on.
- Power the control on. The start-up screen appears.
- Press the button next to OK to enter the start-up sequence.
- Enter the required values with the rotary dial and the function keys.
- Check each value against the programming table for the system example.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.