Viessmann Boiler: Set the AUX demand set point (DMD SetP)
Set the AUX demand set point (DMD SetP) on a Viessmann boiler: DMD SetP is the fixed set point used when the AUX demand contact is closed. Default input function is demand.
Applies to: Versatronik 300 Cascade Control, AUX demand
How to fix set the aux demand set point (dmd setp): step by step
- Press and hold ENTER for 5 seconds.
- Press the up arrow until Specifications appears and press ENTER.
- Press the up arrow until DMD SetP shows and press ENTER to edit.
- Use up or down to change the value, then press ENTER to save.
- Press ESC to exit. The displayed set point should match the demand set point and an A should show.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
More settings shortcuts tips for boiler
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.