Settings shortcuts: Boiler tips (part 8 of 10)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on settings shortcuts for boiler. Check each one against the manual for your exact model before acting.

Set increased DHW hygiene (weekly or daily heating above 140°F)

Viessmann · DHW tank with sensor control

Heats the DHW tank above 140°F (60°C) once a week or for an hour every day at the set time. Not valid for systems with a DHW tank with temperature switch (such as an Aquastat).

  1. Open DHW, then Hygiene function.
  2. Set the start time.
  3. Select the required day or every day.
  4. Confirm.
  5. To switch off, deselect the day or every day and confirm.

Set individual DHW heating cycles for each day of the week

Viessmann · Vitotrol 300 remote control, DHW time program

Set different DHW heating cycles for each weekday instead of one cycle set for all days. Up to four cycles per day can be set.

  1. Open the flip-down cover of the remote control.
  2. Select 'Time Program DHW' and wait for the display to show it.
  3. Select 'Individual?' and confirm.
  4. Use the up/down keys to choose the weekday to change.
  5. Select 'DHW Heating Cycle 1' and then 'DHW Heating Cycle 1 On'.
  6. Use the up/down keys to set the start time, then confirm. The display switches to 'Cycle 1 Off'.
  7. Use the up/down keys to set the end time, then confirm. The display switches to 'Cycle 2 On'.
  8. Set cycles 2 to 4 the same way.
  9. Close the flip-down cover.
  10. To end settings early, press the back/cancel key again. To skip a cycle, press the skip key.

Set individual DHW time cycles

Viessmann · Vitotronic 300 Model GW2

Sets up to 4 DHW (or DHW re-circulation pump) cycles, either identical for all days or per day.

  1. Select individual DHW time program mode as described above.
  2. Use up or down to select '1-7' for all days, or a single day such as 'Mo'.
  3. Press OK; cycle 1 appears. Press OK again to set its start time, using up or down, and confirm.
  4. Set the finish time with up or down and confirm.
  5. Repeat for DHW cycles 2 to 4; to skip a cycle, press the skip button.
  6. Close the hinged cover.

Set maximum burner output

Viessmann · CA3B Series 2.5 to 6.0

Changes the maximum operating output of the burner in percent. Stay inside the modulation range given on page 67.

  1. Hold the S button for more than 2 seconds until the indicator flashes.
  2. Turn the dial until 6 shows under Service.
  3. Press S. A 6 shows under Status.
  4. Press S. A 1 shows under Status and the current maximum output (%) shows under Service.
  5. Use Y or B to set the required maximum output.
  6. Press S to confirm. A 1 under Service means success, 0 means it failed.
  7. Press S to return to the operating display.

Set maximum heating output

Viessmann · Vitocrossal 300 CU3A heating output limit

Limits heating output through the modulation range. The upper limit is also set by the boiler coding card.

  1. Press OK and the second button together for about 4 seconds (button symbol not legible in source).
  2. Select "Service functions".
  3. Select "Max. output".
  4. Select "Change?" then "Yes". A value flashes (e.g. 85), which equals 100% of rated output in the delivered condition.
  5. Set the required value.

Set maximum operational burner input

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

Change the maximum burner output in percent from the burner control unit. The value must stay within the modulation range shown on page 19.

  1. Hold the S button for more than 2 seconds until the indicator flashes.
  2. Press Y until "6" shows under Service.
  3. Press S. "6" shows under Status.
  4. Press S. "1" shows under Status and the current maximum output in % shows under Service.
  5. Use Y or B to set the required maximum output.
  6. Press S to confirm. "1" under Service means success, "0" means it failed.
  7. Press S to return to the operating display.

Set measuring units

Viessmann · Control

Choose metric or imperial units for the display.

  1. Press Menu, then Settings, then Measuring units.
  2. Select Metric or Imperial.
  3. Press OK to confirm.

Set normal and reduced room temperature

Viessmann · Vitotronic 300-K MW1S heating circuits

Normal room temperature is set with the set value adjuster. Reduced (night) temperature is set separately.

  1. For normal room temperature, turn the set value adjuster to the required day temperature. The value is taken over after about 2 seconds.
  2. For reduced room temperature, call up the reduced night temperature with its button.
  3. Change the value with the arrow buttons.
  4. Press OK to confirm.

Set operator-requested boiler sequence

Viessmann · Boiler sequence selection

Selects an alternative boiler lead order shown without hyphens. The chosen sequence is a request and may not match the actual sequence.

  1. Open the hinged cover on the programming unit.
  2. Press the two adjust buttons together for about 2 seconds; the requested sequence (no hyphens) shows.
  3. Adjust with up or down until the required sequence shows.
  4. Confirm; the display returns to the actual boiler sequence.
  5. Close the hinged cover.

Set or cancel the holiday program

Viessmann · Vitotronic 300-K, MW2C

The holiday program applies to all heating circuits. Circuits on 'Heating and DHW' run at the reduced room temperature. Circuits on 'DHW only' get no central heating. In both cases boiler and DHW tank frost protection stays active. DHW heating is off and only tank frost protection runs. The program starts at 00:00 h on the day after departure and ends at 00:00 h on the return date, so the standard time program runs on both those days. Changes to the program are made by the heating contractor.

  1. From the home screen, select 'Holiday program'.
  2. To set it, enter the departure date and the return date, then confirm.
  3. To cancel or delete it, select 'Holiday program' from the home screen and use the delete option.

Set standard and reduced room temperature

Viessmann · Vitotronic 300-K heating circuits

The standard room temperature and the reduced room temperature are set in the operating menu. The manual shows example settings: standard 68 to 79°F (20 to 26°C), and reduced 37 to 57°F (3 to 14°C). The adjustment steps are in the Operating Instructions, not this manual.

  1. Refer to the Operating Instructions for the adjustment steps.
  2. Confirm the standard setpoint, for example 68 to 79°F (20 to 26°C).
  3. Confirm the reduced setpoint, for example 37 to 57°F (3 to 14°C).

Set standard and reduced room temperatures

Viessmann · Heating circuits with room temperature setpoints

Example ranges from the manual: standard room temperature changed from 20 C to 26 C (68 F to 79 F); reduced room temperature changed from 5 C to 14 C (41 F to 57 F). The adjustment itself is made as described in the Operating Instructions.

  1. Refer to the Operating Instructions to change the standard room temperature.
  2. Refer to the Operating Instructions to change the reduced room temperature.

Set target supply temperature for a heating zone or circuit

Viessmann · Heating zones and heating circuits

Sets the target supply temperature for a selected heating zone or heating circuit.

  1. Open the "Heating" function.
  2. Select the heating zone or heating circuit and confirm.
  3. Adjust the target supply temperature.
  4. Confirm.

Set temperature units

Viessmann · Vitotronic 300-K, MW2C

Choose metric or imperial units for displayed values.

  1. From the home screen, open 'Settings' and select 'Temperature units'.
  2. Select 'Metric' or 'Imperial' and confirm.

Set the AUX demand set point (DMD SetP)

Viessmann · Versatronik 300 Cascade Control, AUX demand

DMD SetP is the fixed set point used when the AUX demand contact is closed. Default input function is demand.

  1. Press and hold ENTER for 5 seconds.
  2. Press the up arrow until Specifications appears and press ENTER.
  3. Press the up arrow until DMD SetP shows and press ENTER to edit.
  4. Use up or down to change the value, then press ENTER to save.
  5. Press ESC to exit. The displayed set point should match the demand set point and an A should show.

Set the boiler sequence in a cascade

Viessmann · Multi boiler cascade

The control offers several boiler sequences, depending on the coding and the internal control calculations. The sequence is set so the boilers run evenly. Boiler numbers are fixed. The sequence shows the order in which boilers start. The example on the page shows Boiler 5, then Boiler 1, 2, 3 and 4.

  1. Press Menu, then Boiler sequence.
  2. Select New boiler sequence.

Set the central heating time program

Viessmann · Vitotronic 300-K, MW1B and Vitotronic 100, GC1B

Sets the start and end of each standard heating time phase for each day or part of the week. Outside these phases the rooms run at reduced temperature.

  1. Open the extended menu.
  2. Select "Heating".
  3. Select the heating circuit if needed.
  4. Select "Heating time program".
  5. Select the part of the week or a single day.
  6. Select the time phase (!, ?, § or $).
  7. Set the start and end times for that phase.
  8. Press to exit the menu.

Set the date and time

Viessmann · Vitotrol 300 remote control

Time and date are factory set and can be changed by hand on the remote control.

  1. Open the flip-down cover of the remote control.
  2. Select 'Time' and press to enter the time setting.
  3. Use the up/down keys to set the time, then confirm.
  4. The date is shown next. Use the up/down keys to set it, then confirm.
  5. Close the flip-down cover.

Set the DHW operating program

Viessmann · DHW heating

The factory setting is Heating and DHW. If no central heating is needed, set DHW only. The operating programs are described in the Terminology section of the manual.

  1. Set the DHW operating program to Heating and DHW, or to DHW only if central heating is not needed.

Set the DHW target temperature

Viessmann · DHW tank with sensor control

Do not set DHW below 122°F (50°C) for hygiene reasons. Not valid for systems with a DHW tank with temperature switch (such as an Aquastat).

  1. On the DHW default display, select the target value.
  2. Set the required value.
  3. Confirm.

Set the DHW temperature

Viessmann · Vitotronic 300-K, MW1B

Sets the stored hot water target temperature.

  1. Open the extended menu.
  2. Select "DHW".
  3. Select "Set DHW temperature".
  4. Set the required value.

Set the DHW time program

Viessmann · Vitotronic 300-K, MW1B

Automatic mode reheats DHW during standard heating times and starts 30 minutes before the heating phase. Individual mode allows up to 4 phases per day.

  1. Open the extended menu.
  2. Select "DHW".
  3. Select "DHW time prog".
  4. Select "Individual" if automatic mode is not wanted.
  5. Select the part of the week or a single day.
  6. Select the time phase (!, ?, § or $).
  7. Set the start and end times for that phase.
  8. Press to exit the menu.

Set the DHW time program (cycles 1 to 4)

Viessmann · Vitotronic 300 GW2, DHW time program

Sets the start and end times of up to four domestic hot water heating cycles, either the same for all days or per weekday. The DHW re-circulation pump follows the same program.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the DHW time program button and select '1-7' for identical cycles every day, or a single weekday (Mo, Tu, etc.) for different cycles.
  4. Confirm. The display moves to DHW time cycle 1.
  5. Press the button to reach DHW cycle 1 ON, then set the start time and confirm.
  6. Set the finish time for DHW cycle 1 and confirm.
  7. Repeat for DHW cycles 2 to 4 with the same method. Press the skip button to leave a cycle unused.
  8. Close the cover when finished.

Set the display brightness

Viessmann · Control unit display

Adjusts the brightness of the control unit display.

  1. Call up the home screen.
  2. Select Settings, then confirm with OK.
  3. Select Display brightness, then confirm with OK.
  4. Select Display, then confirm with OK.
  5. Select the required value, then confirm with OK.
  6. Press and hold the exit button for about 4 sec to leave the menu.

Set the holiday program

Viessmann · Heating program rw or w

With the 'rw' heating program, heating continues at the reduced room temperature during the holiday, without DHW heating. With the 'w' program, only freeze-up protection runs, and DHW heats per the time program on departure and return dates. The holiday program applies to all heating circuits unless the installer changes it.

  1. Open the cover on the programming unit.
  2. Press the holiday program button; the holiday display appears.
  3. Press confirm, then use the up or down button to set the departure date and confirm.
  4. Set the return date with the up or down button and confirm.
  5. With 'rw' selected, press the reduced temperature button, set the value and confirm.
  6. Close the cover.

Set the home screen (default display)

Viessmann · Control panel

Choices are 'Heating circuit' or 'Continuous operation', 'DHW', or 'Device status'. Available options depend on whether the system runs weather-compensated or constant operation.

  1. Open Settings.
  2. Select 'Selecting the default display'.
  3. Select the required display.
  4. Confirm.
  5. Tap the home screen to call up the selected display.

Set the operating program

Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Chooses between DHW only and Heating and DHW for a heating circuit. The default is Heating and DHW.

  1. From the home screen, open Menu, then Heating.
  2. Select the heating circuit.
  3. Open Operating program.
  4. Select DHW only or Heating and DHW.
  5. Press OK to confirm.

Set the room temperature setback

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Example: change the setback from 41°F to 57°F (5°C to 14°C).

  1. Open the menu.
  2. Select Heating.
  3. Select the heating circuit.
  4. Press OK.
  5. Select the reduced room temperature setpoint and press OK.
  6. Change the value with the arrow keys.
  7. Accept with OK.
  8. Return to the standard menu.

Set the standard room temperature

Viessmann · Vitotrol 200A remote control

Sets the room temperature used during standard heating mode. Factory setting is 68°F (20°C).

  1. Press +/- to set the required standard room temperature.
  2. Press OK to confirm.
  3. The display then shows the current (actual) room temperature.

Set the standard room temperature and time program

Viessmann · Vitotronic 300 GW6C control

The standard room temperature is used when occupied. Reduced room temperature applies at night or when absent. A time program sets phases for day and night. The standard room temperature should not be set above 68°F (20°C).

  1. Set the standard room temperature in the standard menu, no higher than 68°F (20°C).
  2. Set the reduced room temperature for night and absence.
  3. Set the time program so the standard temperature runs during the day and the reduced temperature at night.
  4. Use Comfort mode to heat outside the time program for a set period.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.