Applies to: Vitotronic 300 GW2
How to fix service level overview: step by step
- Temperatures, boiler coding cards and scans: menu and reset buttons together for about 2 seconds, exit with OK (p. 73).
- Relay test: menu and OK together for about 2 seconds, exit with OK (p. 68).
- LON participant check: w and OK together for about 2 seconds, exit by pressing w and OK for about 1 second (p. 66).
- Operating status information: press the status button (p. 77).
- Service scan (when Service is flashing): press OK (p. 74).
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Vitotronic 300 GW2 installation and service instructions, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.