Viessmann Boiler: Seal test for flue gas leaks during operation
Seal test for flue gas leaks during operation on a Viessmann boiler: Leak check of burner door and flue gas components while the boiler runs. Viessmann says to check with the boiler at operating temperature.
Applies to: Vitocrossal 200 CI2 gas condensing boilers
Common causes of seal test for flue gas leaks during operation
- Gasket leaks on burner door or flue gas components
- Leaks at flue gas collector or insulation
How to fix seal test for flue gas leaks during operation: step by step
- Check gaskets on the burner door and flue-gas-carrying components with an inspection mirror while the boiler is running.
- If needed, remove the thermal insulation parts to see the components.
- Look for condensate on the outside of the flue gas collector or insulation, which indicates a leak.
- Check the burner settings with the boiler heated to operating temperature (min. 40°C/104°F).
- Also check the burner at partial load.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Service Instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.