Viessmann Boiler: Reset after auxiliary low gas pressure switch fault
Reset after auxiliary low gas pressure switch fault on a Viessmann boiler: The burner stops and fault C1 is shown when gas pressure falls below the switch setting.
Applies to: Auxiliary low gas pressure switch
Common causes of reset after auxiliary low gas pressure switch fault
- Gas supply pressure is below the minimum operating pressure of 4.5 in. w.c.
How to fix reset after auxiliary low gas pressure switch fault: step by step
- Press the low gas pressure switch reset button once.
- Reset the boiler control fault.
- If the fault returns, check the gas supply pressure.
- Contact the local gas company if the supply is below 4.5 in. w.c.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.