Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Replacing the burner door

Updated · by Aurora Star Tech Inc.

Replacing the burner door on a Viessmann boiler: Removes the fan, venturi, gas train and burner control from the burner door, then swaps the door. Leak test the gas line after reconnecting it.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CM2 186 to 311 burner door

How to fix replacing the burner door: step by step

  1. Loosen the retaining clamp and disconnect the combustion air flex hose; set it aside.
  2. Disconnect the gas line.
  3. Disconnect electrical plugs 35, 36, 87, 111 and 122 from the burner control. Remove the burner control cover (see p. 30) to reach plugs 87 and 111.
  4. Disconnect plugs 100 and 100A from the fan. Disconnect pressure switch tubes APS1 from the venturi and APS2 from the burner door.
  5. Remove the four M8 (13 mm hex) nuts holding the fan to the burner door. Remove the fan/venturi/gas train assembly and set it aside.
  6. Remove the two M6 bolts and the burner control assembly.
  7. Remove the ignition and ionization electrode block (see p. 36).
  8. Remove the cotter pins and hinge pins from the burner door.
  9. Remove the four M12 (19 mm hex) burner door bolts and washers.
  10. Disconnect plugs 40/156 and 40 from the burner control bracket, and plugs 90 and 41 from the burner control. Replace the barb fitting washer if needed.
  11. Remove the burner tube (see p. 39).
  12. Install the new burner door and attach the door studs for the fan/venturi assembly.
  13. Torque the M8 nuts to 53 lb.in (6 Nm) and the M12 door bolts to 13 lb.ft (18 Nm).
  14. Reinstall in reverse order and leak test the reconnected gas line.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 40. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977