Replacing the burner door refractory on a Viessmann boiler: Removes the refractory, rope seal and insulation from the burner door. Refit with the same torque as the burner door.
Applies to: Vitocrossal 200 CM2 186 to 311 burner door
How to fix replacing the burner door refractory: step by step
- Loosen the retaining clamp and disconnect the combustion air flex hose; set it aside.
- Disconnect the gas line.
- Remove the ionization electrode block and the ignition electrode block.
- Remove the six M12 (19 mm hex) burner door bolts and washers.
- Remove the burner tube (see p. 39). Replace the burner tube gasket if needed.
- Remove the rope seal. When refitting, apply high temperature silicone to hold it in place.
- Remove the refractory, the electrode block insulation and the insulation blanket.
- Reinstall in reverse order. Torque the M12 door bolts to 13 lb.ft (18 Nm).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 41. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.