Viessmann Boiler: Replace plug console with relay
Replace plug console with relay on a Viessmann boiler: Plug console that carries the relay contactor.
Applies to: Plug console with relay
How to fix replace plug console with relay: step by step
- Unplug plugs 40/156 and 40 from the back of the plug console.
- Disconnect the two yellow/green ground wires from the terminal block below the console.
- Disconnect wires T1 (brown) and T2 (blue) from the relay contactor.
- Remove the four 3 mm hex head screws and washers from the mounting plate.
- Fit the new plug console with relay.
- Reassemble in reverse order.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.