Viessmann Boiler: Replace ionization electrode block
Replace ionization electrode block on a Viessmann boiler: Replaces the flame sensing electrode block on the burner door. Use only the new parts from the kit.
Applies to: Ionization electrode
How to fix replace ionization electrode block: step by step
- Disconnect the ionization cable from the electrode terminal.
- Remove the four M12 burner door bolts and washers. Disconnect the gas line and plugs 40/156, 53 and 40 from the burner control bracket, and plugs 90 and 41 from the burner control.
- Open the burner door.
- Remove the electrode terminal nut, serrated washer and O-ring. Remove the inner electrode.
- Remove the two M6 screws and washers, then the electrode block and gasket. Discard the block.
- Fit the new block and gasket with new parts from the kit.
- Check the electrode-to-burner dimension against the drawing and adjust carefully if needed.
- Tighten the M12 burner door bolts and the M6 electrode screws to the torque in the torque table.
- Leak test the reconnected gas line.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.